Omron SYSMAC CS Series Operation Manual page 136

Analog i/o units
Hide thumbs Also See for SYSMAC CS Series:
Table of Contents

Advertisement

CS1W-PMV02 Isolated-type Analog Output Unit
Specifications
Item
Model
Applicable PC
Unit classification
Mounting position
Maximum number of Units
Unit numbers
Areas for data
CIO Area words
exchange with
allocated for
CPU Unit
Special I/O Units
DM Area words
allocated for
Special I/O Units
Number of outputs
Output signal types
User-defined scaling in industrial
units
Data storage in the CIO Area
Accuracy
Temperature coefficient
Resolution
Output response time
D/A conversion period
Maximum output delay time
Output signal range
Allowable load resistance
Output impedance
Voltage when open between ter-
minals
Answer input function
Current output disconnection
detection function
Function
Rate-of-change
limit
Output high/low
limits
Output hold
Isolation
Insulation resistance
CS1W-PMV02
CS Series
CS-series Special I/O Unit
CS-series CPU Rack or CS-series Expansion Rack (Cannot be mounted to C200H
Expansion I/O Rack or SYSMAC BUS Remote I/O Slave Rack.)
96 (within the allowable current consumption and power consumption range)
00 to 95 (Cannot duplicate Special I/O Unit numbers.)
10 words/Unit
CPU Unit to Analog Output Unit:
Analog output values for each output
Analog Output Unit to CPU Unit:
None
100 words/Unit
CPU Unit to Analog Output Unit:
Output hold for when CPU Unit error occurs, high/low limit values, rate-of-change limit
values, zero/span adjustment for control outputs, etc.
4
0 to 10 V, 0 to 5 V, 0 to 1 V, −10 to 10 V, −5 to 5 V, −1 to 1 V
(Each output point can be set individually.)
Scaling is possible for each of the above signal types individually.
(The data corresponding to the minimum and maximum output values can be set
freely.)
±32,000 (8300 to FFFF Hex, 0000 to 7D00 Hex)
±0.1% of full scale
±0.015%/°C of full scale
−10 to 10 V, −1 to 1 V:
0 to 10 V, 0 to 1 V, −5 to 5 V: 1/8,000 of full scale
0 to 5 V:
50 ms max. (travel time from output 0% to 90%, for step output)
40 ms/4 outputs
Output response time + conversion period + one CPU Unit cycle
–15 to 115% (–7.5 to 107.5% for ±10-V and ±1-V ranges)
10 kΩ min.
0.5 Ω max.
---
None
None
This function can be used to control the speed of up and down changes in analog out-
put values.
This function can be used to place high and low limits on analog output values.
This function holds the analog output value to the previous value or to a specified pre-
set value when any of the following CPU Unit errors occurs. Normal operation is
restored when the CPU Unit error is cleared.
• CPU Unit fatal error (including FALS execution)
• CPU error in CPU Unit
• CPU Unit's load interrupted
Between outputs and between output terminals and PC signals: Isolation by trans-
former and photocoupler
20 MΩ (at 500 V DC) between outputs
Specifications
1/16,000 of full scale
1/4,000 of full scale
Section 2-10
123