µ-Dimension D4006 User Manual page 36

4000 series control system
Hide thumbs Also See for D4006:
Table of Contents

Advertisement

• USER (default): A double bump calls channel levels
recorded by the user
• MAX: A double bump calls channel levels to go to the
extreme, either 100% (max) or 0% (off).
Backlight
Controls the behavior of the LCD backlight. Settings are as
follows:
• DIMMED: The backlight goes to a dimmed state after 1
minutes of inactivity
• OFF (default): The backlight goes off after 1 minute of
inactivity.
Time Master
All Leviton products which have an integrated time clock support
the time master feature. This feature allows automatic
synchronization of time clocks so all clocks are set to the same
time. This feature is achieved by the master time clock on the
network periodically broadcasting it's time to the network, then,
all other devices setting their clocks to the time of the master
time clock. Valid values for this option are as follows:
• OFF: master time clock is ignored and only the local
settings are used.
• RECV: Receive Only - device will listen to broadcasts from a
master time clock, and set local time to the master time
clock but will never broadcast time.
• MAST: Master - device will always be a Master time clock
and will always broadcast time to the network. Although
the AUTO setting is almost always preferred, in some cases
you may wish to force a device to always be the master. In
this case, only one device on the network should be set to
the MAST setting, all other should be AUTO or RECV. If
upon startup it is detected that a master time clock is
already on the network, this device will automatically
demote itself to the AUTO setting until it's next power-up at
which point it will attempt to re-establish itself as the
master.
• AUTO (default): the preferred setting for this option. In
automatic mode, upon startup this device will listen to the
network to determine if a master time clock is already on
the network. If a master is detected, it will listen to and set