D4104, D4106, D4206 - µ-Dimension D4006 User Manual

4000 series control system
Hide thumbs Also See for D4006:
Table of Contents

Advertisement

Devices with Channel Control & Dimmers

(D4104, D4106, D4206)

Setting up units with control and dimmers require a few basic
steps which when followed will ensure success of your lighting
control system:
Step 1:
Step 2:
Step 3:
Step 4:
Step 5:
Step 6:
Step 7:
Step 8:
Step 9:
Step 10:
Page 11
Confirm all connections have been completed and load
circuits are without fault.
Confirm network is terminated correctly, reference
installation guide for additional information.
Complete all "System Layout Charts" on page 68 to
confirm a clear understanding of all system and
configuration requirements.
Review "Navigating the Menus" on page 49
Power up unit
Perform "Power Up Initialization" on page 16 (or
review "Setting the Network ID" on page 20)
For load types that are not incandescent, adjust
dimmer load types appropriate. See "Configuring
Dimmers" on page 28
If there is more than one master station on the
network, set the starting channel address for this
group of dimmers. Each controller should address it's
own unique range of channels. See "To Assign Zones,
consecutively, from a Starting Channel Number:" on
page 25.
Repeat above steps 4-7 for all other devices on the
network. This is especially critical for other D4006
remote dimmers which will be controlled by this
Master.
Push the MAX button
• CONFIRM that all loads of this device and
any remote dimmer go to full. If they DO,
CONGRATULATIONS! You have made it a
long ways towards a successful
installation. If they DO NOT go to full,
please reference the troubleshooting

Advertisement

Table of Contents
loading

This manual is also suitable for:

D4104D4206D4106D4200

Table of Contents