µ-Dimension D4006 User Manual page 29

4000 series control system
Hide thumbs Also See for D4006:
Table of Contents

Advertisement

Configuration Guide
• Disabled: dimmer will never respond to a blink warn.
Typically you will only want to disable blink warn for a dimmer
when the load connected to that dimmer does not immediately
recover from a loss of power; for example, most HID ballasts
have a long warm-up time before any usable light is output and
as such blink warn should be disabled. However, most fluorescent
types have immediate recover and therefore blink warn may be
enabled.
Blink warns are used to notify the occupant that the lights are
about to be turned off. This notification is in the form of a brief
"blink" off of the lights in the room. After the blink has occurred,
the user has 5 minutes to cancel the event by pressing any of the
normal buttons used to control lighting in the room. If the event
is not cancelled, then, the lights will shut off. If the event is
cancelled, then the lights will remain in their current state for a
time period, then, the process will repeat. Blink - option to cancel
- off or override on. The override time period can be set from the
MISC SETTINGS menu to 30 minutes, 1 hour, or 2 hours.
Maximum
Sets the maximum value of the dimmer. Values are 0-255, 0=0%
output and 255=100% output. Default setting is 255. This setting
may be lowered if the dimmer should never exceed a particular
light output.
Minimum
Sets the minimum value of the dimmer. Values are 0-255, 0=0%
output and 255=100% output. Default setting is 0. This setting
should be raised if the dimmer should never go below a particular
light level. Please note that a level any higher then 0 will not
allow this dimmer to be shut off completely. This setting is useful
for night lights which never go off completely.
Cutoff
Sets the lowest level before the dimmer will immediately go off.
Valid values are 0-255, default value varies by dimmer types. If
you're having trouble with ballasts flickering at low levels, raising
this value slightly may resolve the problem.