Specification type T thermocouple
Temperature measurement thermo-
couple
Used electrical measuring range
Measuring range, technically usable
Full scale value (FSV)
Measuring range, recommended
PDO LSB
Uncertainty in the
@ 23°C
recommended
ambient temperature
measuring range,
@ 55°C
with averaging
ambient temperature
Temperature coefficient
(change of measured value with change
of terminal ambient temperature)
Fig. 40: Measuring uncertainty for type T thermocouple
ELX3312 and ELX3314
Type T
±75 mV
-270°C ≈ -6.258 mV ... +400°C ≈ 20.872 mV
+400°C
-100°C ... +400°C
0.1/0.01°C/digit, depending on PDO setting
± 2.6 K ≈ ± 0.65 %
FSV
± 2.9 K ≈ ± 0.73 %
FSV
Since the value is strongly dependent on the sensor temperature,
as can be seen in the specification plot below, it can be derived
from the specification plot. For a better approximation, the
measurement uncertainty at T
average value between 23°C and 55°C to illustrate the non-linear
relation.
Version: 1.3.0
Basic function principles
= 39°C is also shown as the
amb
53