Producer Codeword - Beckhoff ELX3312 Operating Manual

Two and four channel analog input terminals for thermocouples, 16 bit, ex i
Hide thumbs Also See for ELX3312:
Table of Contents

Advertisement

Parameterization and programming
The terminal constantly records measured values and saves the raw values from its A/D converter in the
ADC raw value objects 0x80nE:01, 0x80nE:02. After each recording of the analog signal, the correction
calculation takes place with the vendor and user calibration data as well as the user scaling, if these are
activated (see following picture).
Fig. 43: Calculation of process data
Calculation
Calculation
X
ADC
X
F
-14
Y
= (X
– B
) x A
x 2
H
ADC
H
H
-14
Y
= (Y
– B
) x A
x 2
A
H
A
A
-16
Y
= Y
x A
x 2
+ B
S
A
S
S
Key
Name
Designation
X
Output value of the A/D converter
ADC
X
Output value after the filter
F
B
Vendor calibration offset (not changeable)
H
A
Vendor calibration gain (not changeable)
H
B
User calibration offset (can be activated via index 0x80n0:0A)
A
A
User calibration gain (can be activated via index 0x80n0:0A)
A
B
User scaling offset (can be activated via index 0x80n0:01)
S
A
User scaling gain (can be activated via index 0x80n0:01)
S
Y
Process data for controller
S
Measurement result
The accuracy of the result may be reduced if the measured value is smaller than 32767 / 4 due to
one or more multiplications.
Also see about this
2 Configuration data (vendor-specific) [} 75]
5.3.7

Producer Codeword

Producer Codeword
The vendor reserves the authority for the basic calibration of the terminals. The Producer codeword
is therefore at present reserved.
60
Designation
Output of the A/D converter
Output value after the filter
Measured value after vendor calibration,
Measured value after vendor and user calibration
Measured value following user scaling
Version: 1.3.0
Index
0x80nE:01
-
0x80nF:01
0x80nF:02
0x80n0:17
0x80n0:18
0x80n0:11
0x80n0:12
-
ELX3312 and ELX3314

Advertisement

Table of Contents
loading

This manual is also suitable for:

Elx3314

Table of Contents