Basic function principles
Specification type S thermocouple
Temperature measurement thermo-
couple
Used electrical measuring range
Measuring range, technically usable
Full scale value (FSV)
Measuring range, recommended
PDO LSB
Uncertainty in the
@ 23°C
recommended
ambient temperature
measuring range,
@ 55°C
with averaging
ambient temperature
Temperature coefficient
(change of measured value with change
of terminal ambient temperature)
Fig. 39: Measurement uncertainty for type S thermocouple
52
Type S
±75 mV
- 50°C ≈ -0.236 mV ... +1768°C ≈ 18.693 mV
+1768°C
+250°C ... +1700°C
0.1/0.01°C/digit, depending on PDO setting
Note:
Internally, 16 bits are calculated on the measuring range end
value. Depending on the thermocouple set, there are value jumps
> 0.01°C; at "Resolution 0.01°C"; Type S: app. 0.05°C
± 3.4 K ≈ ± 0.19 %
FSV
± 4.4 K ≈ ± 0.25 %
FSV
Since the value is strongly dependent on the sensor temperature,
as can be seen in the specification plot below, it can be derived
from the specification plot. For a better approximation, the
measurement uncertainty at T
average value between 23°C and 55°C to illustrate the non-linear
relation.
Version: 1.3.0
= 39°C is also shown as the
amb
ELX3312 and ELX3314