Fig. 57: Selection of the process data
The safety address together with the CRC must be entered on the TwinSAFE SC slave side. This is done via
the CoE objects under TSC settings of the corresponding TwinSAFE SC component (here, for example,
EL5021-0090, 0x8010: 01 and 0x8010: 02). The address set here must also be set in the alias device as
FSoE address under the Linking tab.
Under the object 0x80n0:02 Connection Mode the CRC to be used is selected or a free CRC is entered. A
total of 8 CRCs are available. A free CRC must start with 0x00ff in the high word.
Fig. 58: CoE objects 0x8010:01 and 0x8010:02
Object TSC Settings
Depending on the terminal, the index designation of the configuration object TSC Settings can vary.
Example:
- EL3214-0090 and EL3314-0090, TSC Settings, Index 8040
- EL5021-0090, TSC Settings, Index 8010
- EL6224-0090, TSC Settings, Index 800F
Fig. 59: Entering the safety address and the CRC
ELX3312 and ELX3314
Version: 1.3.0