Trane Tracer UC600 Integration Manual page 32

For packaged outdoor air unit
Table of Contents

Advertisement

O O b b j j e e c c t t a a n n d d D D i i a a g g n n o o s s t t i i c c D D a a t t a a P P o o i i n n t t s s
Table 10. All object types sorted by object name (continued)
Object Type
Object Name
Space Temperature
AV37
Setpoint Active
Space Temperature
AV25
Setpoint BAS
Space Temperature
AI20
Setpoint Local
Supply Air Flow Active
AV41
Supply Air Flow Setpoint
AV39
Supply Fan Pressure
AI3
Local
Supply Fan Start Stop
BO1
Command
Supply Fan Status
BI1
System LOCKOUT
BV17
BV28
Thumbwheel Installed
Unoccupied Cooling
BV23
Mode
Unoccupied Cooling
BV22
Mode BAS
Unoccupied Cooling
AV26
Setpoint
Unoccupied Dehumid
BV40
Mode
Unoccupied Dehumid
BV37
Mode BAS
Unoccupied Dewpoint
AV28
Setpoint
Unoccupied Heating
BV39
Mode
Unoccupied Heating
BV38
Mode BAS
Unoccupied Heating
AV27
Setpoint
BV43
Ventilation Mode
Water Coil Low Temp
BI9
Switch
BI8
Water Flow
Y1 Space Lockout
BV35
AI8
Zone CO
Local
2
32
Min / Max
When the Point Exists
Units that are Space
45 to 95 °F
Control or Single Zone
VAV.
Units that are Space
-58 to 482 °F
Control or Single Zone
VAV.
Units with Thumbwheel
50 to 86 °F
Installed.
Units with Piezo Ring on
0 – 15000 cfm
Supply Fan.
OAB or OAG units that are
0 – 7500 cfm
208v or 460v.
Units with Piezo Ring on
0 - 25 in(H
O)
2
Supply Fan.
All Units.
All Units.
All Units.
All Units.
All Units.
All Units.
Units with Space
60 – 90 °F
Temperature/Humidity
Sensor Installed.
All Units.
All Units.
Units with Space
49 – 100 °F
Temperature/Humidity
Sensor Installed.
All Units.
All Units.
Units with Space
45 - 90 °F
Temperature/Humidity
Sensor Installed.
Units that are Space
Control, Single Zone VAV,
or Discharge Control.
Units that are Water
Source Heat Pump.
Units that are Water
Source Heat Pump.
Units that are Space
Control or Single Zone
VAV.
0 – 3000
Units with a CO
ppm
Installed.
Description
Actively used space
temperature setpoint.
Communicated space
temperature setpoint.
Local thumbwheel input.
Actively used supply airflow.
Setpoint used to modulate the
indoor fan speed.
Local supply fan piezo ring
pressure.
Normally Closed Input • 0 = On
• 1 = Off
Normally Closed Input • 0 = On
• 1 = Off
Latching diagnostic. Cleared
with Alarm Reset. • 0 = Normal
• 1 = Fail
• 0 = Not Installed • 1 =
Installed
• 0 = Disabled • 1 = Enabled
• 0 = Disabled • 1 = Enabled
Space cooling setpoint used in
unoccupied mode.
• 0 = Disabled • 1 = Enabled
• 0 = Disabled • 1 = Enabled
If the space dewpoint rises
above this setpoint during
unoccupied mode then
dehumidification will be
enabled.
• 0 = Disabled • 1 = Enabled
• 0 = Disabled • 1 = Enabled
Space heating setpoint used in
unoccupied mode.
• 0 = Disabled
• 1 = Enabled
Normally closed input.
• 0 = Open
• 1 = Closed
Normally open input.
• 0 = Off
• 1 = On
• 0 = Disabled
• 1 = Enabled
Sensor
2
Local Space CO
concentration
2
BAS-SVP18D-EN