O O b b j j e e c c t t a a n n d d D D i i a a g g n n o o s s t t i i c c D D a a t t a a P P o o i i n n t t s s
Table 5. Analog values (continued)
Object Type
Object Name
Minimum OA Damper
AV48
Position
Duct Static Pressure
AV49
Setpoint
Space CO
2
AV50
Concentration Setpoints
Cooling Capacity
AV52
Duct Static Pressure
AV53
Setpoint Active
AV54
Exhaust Air Flow Active
Return Duct/Space
AV56
Pressure Setpoint
Exhaust Air Flow
AV57
Setpoint
Pre-Heat Enable
AV58
Temperature
Minimum Supply Air
AV59
Flow Setpoint
AV64
Duct Static Pressure BAS
Duct Static Pressure
AV65
Active
Discharge Air
AV66
Temperature Setpoint
Active
Discharge Air
AV67
Temperature Setpoint
BAS
Discharge Air
AV68
Temperature Setpoint
Heat/Cool Mode
AV69
Deadband
Maximum Supply Air
AV70
Flow Setpoint
Outdoor Air Minimum
AV71
Flow Setpoint
Outdoor Air Minimum
AV72
Flow Setpoint Active
Outdoor Air Temperature
AV75
BAS
Outdoor Air Temperature
AV76
Active
Outdoor Air Humidity
AV81
BAS
Outdoor Air Humidity
AV82
Active
22
Min / Max
When the Point Exists
Units with Modulating
0 – 100 %
Dampers.
-1 to 6 in(H
O)
Units with Multi Zone VAV.
2
0 – 3000 ppm
All Units.
Units with DX Cooling.
0 – 100 %
-1 to 6 in(H
O)
Unit with Multizone VAV.
2
Units with Piezo Ring on
0 – 15000 cfm
the Exhaust Fan.
Units with Modulating
0 - 2 in(H
O)
Dampers and Exhaust Fan
2
(s).
OAB or OAG units that are
208v or 460v, and does
not have Modulating
0 – 7500 cfm
Dampers with Exhaust Fan
(s).
Units with an ERV and an
-10 to 35 °F
Electric Pre-Heater.
Units with Single Zone or
300 – 13500 cfm
Multi Zone VAV.
-6 to 6 in(H
O)
Units with Multi Zone VAV.
2
-6 to 6 in(H
O)
Units with Multi Zone VAV.
2
38 – 130 °F
Units with Multi Zone VAV.
45 – 90 °F
Units with Multi Zone VAV.
45 – 120 °F
Units with Multi Zone VAV.
-58 to 482 °F
Units with Multi Zone VAV.
Units with Single Zone or
350 – 13500 cfm
Multi Zone VAV.
Units that are VAV, have
Outdoor Air Flow
350 – 13500 cfm
Monitoring, and
Modulating Dampers.
Units that are VAV, have
Outdoor Air Flow
350 – 13500 cfm
Monitoring, and
Modulating Dampers.
-100 to 200 °F
All Units.
-100 to 200 °F
All Units.
0 - 100%
All Units.
0 - 100%
All Units.
Description
Minimum outdoor air damper
position.
Setpoint used to modulate
indoor fan.
Space CO
concentration
2
Setpoints
Primary cooling source
capacity.
Actively used duct static
pressure setpoint.
The amount of air delivered by
the exhaust fan.
Setpoint used to modulate
exhaust fan speed.
Setpoint used to modulate
exhaust fan speed.
Below this temperature pre-
heat will be enabled.
Supply air flow is limited to not
fall below this number.
Communicated duct static
pressure.
Actively used duct static
pressure.
Actively used discharge air
temperature setpoint.
Communicated discharge air
temperature setpoint.
Discharge air temperature
setpoint.
Heat is enabled when Outdoor
Air Temperature drops below
Discharge Temperature
Setpoint
- Heat/Cool Mode Deadband.
Cooling is enabled when
Outdoor Air temperature rises
above the Discharge
Temperature Setpoint.
Supply air flow is limited to not
exceed this number.
Setpoint to modulate the
dampers.
Actively used setpoint to
modulate the dampers.
Communicated outdoor air
temperature.
Actively used outdoor air
temperature.
Communicated outdoor air
relative humidity.
Actively used outdoor air
relative humidity.
BAS-SVP18D-EN