Table 10. All object types sorted by object name (continued)
Object Type
Object Name
Outdoor Air Humidity
AV81
BAS
Outdoor Air Minimum
AV71
Flow Setpoint
Outdoor Air Minimum
AV72
Flow Setpoint Active
Outdoor Air Minimum
AV13
Flow Setpoint BAS
Outdoor Air Relative
AI22
Humidity Local
Outdoor Air Temperature
AV76
Active
Outdoor Air Temperature
AV75
BAS
Outdoor Air Temperature
AI21
Local
AO4
PEVFD Command
PEVFD Setpoint
AV40
BO10
Powered Exhaust Enable
BO13
Pre-Heat Enable
Pre-Heat Enable
AV58
Temperature
Pre-Purge Status
BV33
Program Control Type
MV13
Return Air Damper
BV18
Option
Return Air Humidity Local
AI14
Return Air Temperature
AI6
Local
Return Duct/Space
AI12
Pressure Local
Return Duct/Space
AV56
Pressure Setpoint
Space CO2
AV50
Concentration Setpoint
Space Dewpoint Active
AV35
Space Dewpoint Setpoint
AV34
(SPDS)
Space Occupancy
AI16
Request Override
Space Relative Humidity
AI2
Local
Space RH Active
AV7
Space RH BAS
AV8
Space Temp/Humidity
BV20
Sensor Installed
Space Temperature
AV23
Active
Space Temperature BAS
AV20
Space Temperature Local
AI1
BAS-SVP18D-EN
Min / Max
When the Point Exists
0 - 100%
All Units.
Units that are VAV, have
350 -
Outdoor Air Flow
13500
Monitoring, and
cfm
Modulating Dampers.
Units that are VAV, have
350 -
Outdoor Air Flow
13500
Monitoring, and
cfm
Modulating Dampers.
VAV Units with Outdoor air
0 - 13500
flow Monitoring and
cfm
Modulating Dampers.
0 - 100%
All Units.
-100 to
All Units.
200 °F
-100 to
All Units.
200 °F
-50 to 135
All Units.
°F
Units with Powered
0 – 100%
Exhaust.
OAD, OAK, or OAN that
does NOT have
0 - 100%
Modulating Dampers or
Powered Exhaust.
Units with Isolation
Dampers or has Dual Point
Power.
Units with Pre-Heat.
Units with an ERV and an
-10 to 35 °F
Electric Pre-Heater.
Units with Gas as the
Primary Heat.
All Units.
All Units.
Units with Modulating
0 - 100%
Dampers.
Units with Modulating
-25 to 135
Dampers.
°F
Units with Powered
0 - 2 in(H
O)
Exhaust and Modulating
2
Dampers.
Units with Modulating
0 - 2 in(H
O)
Dampers and Exhaust
2
Fan(s).
0 – 3000
All Units.
ppm
-58 to 482
All Units.
°F
Units with Space Control,
-10 – 150
Discharge Control, or
°F
Single Zone VAV.
Units with Thumbwheel
-58 to 482
Installed.
Units with Space Humidity
0 – 100%
Sensor Installed
-150 to
Units with Space Humidity
150%
Sensor Installed.
-150 to
All Units.
150%
Units that are Space
Control or Single Zone
VAV.
-58 to 482
All Units.
°F
-58 to 482
All Units.
°F
Units with Space
-25 to 135 °F
Temperature Sensor
Installed
O O b b j j e e c c t t a a n n d d D D i i a a g g n n o o s s t t i i c c D D a a t t a a P P o o i i n n t t s s
Description
Communicated outdoor air
relative humidity.
Setpoint to modulate the
dampers.
Actively used setpoint to
modulate the dampers.
air flow setpoint used to
modulate dampers.
Local outside air humidity
sensor.
Actively used outdoor air
temperature.
Communicated outdoor air
temperature.
Local outside air temperature
sensor.
Analog exhaust fan VFD speed.
Fan speed setpoint used to
control the indoor fan speed.
• 0 = Off
• 1 = On
• 0 = Off
• 1 = On
Below this temperature pre-
heat will be enabled.
• 0 = Disabled
• 1 = Enabled
• 1 = Space Control
• 2 = Discharge Control
• 3 = Single Zone VAV
• 4 = Multi Zone VAV
• 0 = Not Installed
• 1 = Installed
Local return air humidity
sensor.
Local return air temperature
sensor.
Local return duct or space
pressure sensor
Setpoint used to modulate
exhaust fan speed.
Space CO2 concentration
setpoint.
Actively used space dewpoint.
If the outdoor air dewpoint is
greater than OADS, the unit
will enable dehumidification.
Local input that overrides
Occupancy Request.
Local space relative humidity
sensor.
Actively used space relative
humidity.
Communicated space relative
humidity.
• 0 = Not Installed
• 1 = Installed
Actively used space
temperature.
Communicated space
temperature.
Local space temperature
sensor.
31