Trane Tracer UC600 Integration Manual page 26

For packaged outdoor air unit
Table of Contents

Advertisement

O O b b j j e e c c t t a a n n d d D D i i a a g g n n o o s s t t i i c c D D a a t t a a P P o o i i n n t t s s
Table 9. Multi-state values (continued)
Object Type
Object Name
Heat Type
MV9
Program Control Type
MV13
Dehumidification System
MV16
Status
Compressor Stage 1
MV21
Status
Compressor Stage 2
MV22
Status
Table 10. All object types sorted by object name
Object Type
Object Name
BV16
Alarm Reset
Auxiliary Heating Mode
BV7
Circuit 1 Condenser
AI4
Coil Temperature Local
Circuit 1 Digital Scroll/
AO3
Variable Speed
Command
Circuit 1 Liquid Line
AI18
Pressure Local
Circuit 1 Reversing Valve
BO16
Circuit 2 Condenser Coil
AI5
Temperature Local
Circuit 2 Digital Scroll/
AO8
Variable Speed
Command
Circuit 2 Liquid Line
AI19
Pressure Local
Circuit 2 Reversing Valve
BO17
Compressor 1 Command
BO11
Compressor 2 Command
BO12
Compressor 3 Command
BO5
Compressor 4 Command
BO6
Compressor Count
AV31
Compressor Heating
AV18
Capacity
26
When the Point
Min / Max
Exists
All Units
All Units.
None/None
All Units.
Units with 1+
Compressors.
Units with 2+
Compressors.
Min / Max
When the Point Exists
All Units.
Units that are Heat Pump.
Units with Head
Pressure Control or an Air
-50 to 200 °F
Source Heat Pump.
Units with Digital Scroll or
0 - 100%
Variable Speed on the first
circuit.
Units with Head Pressure
0 – 500 psi
Control and is an Air
Source Heat Pump.
Units that are Heat Pump.
Units with Head Pressure
Control or an Air Source
-50 -200 °F
Heat Pump.
Units with Digital Scroll or
0 - 100%
Variable Speed on the
second circuit.
Units with Head Pressure
0 – 500 psi
Control and is an Air
Source Heat Pump.
Units that are Heat Pump
and Two Circuits.
Units with 1+
Compressors.
Units with 2+
Compressors.
Units with 3+
Compressors.
Units with 4+
Compressors.
Units with DX Cooling.
0 - 4
Units that are Air Source
or Water Source Heat
0 - 100%
Pumps.
Description
• 1 = No Heat
• 2 = Indirect Fired Gas Heat
• 3 = Electric Heat
• 4 = Other
• 5 = Direct Fired Gas Heat
• 6 = Hot Water/Steam
• 1 = Space Control
• 2 = Discharge Control
• 3 = Single Zone VAV
• 4 = Multi Zone VAV
• 1 = Off
• 2 = On
• 3 = Not Present
• 1 = Off
• 2 = On
• 3 = Not Present
• 1 = Off
• 2 = On
• 3 = Not Present
Description
1 = Reset diagnostics or
lockouts. This will reset ALL
diagnostics or lockouts. If the
condition still exists, the
diagnostic reoccurs.
• 0 = Disabled
• 1 = Enabled
Local condenser coil
temperature sensor on circuit
1.
Analog digital scroll or variable
speed output command.
Local refrigerant pressure
sensor on circuit 1.
• 0 = Off
• 1 = On
Local condenser coil
temperature sensor on circuit
2.
Analog digital scroll or variable
speed output command.
Local refrigerant pressure
sensor on circuit 2.
• 0 = Off
• 1 = On
• 0 = Off
• 1 = On
• 0 = Off
• 1 = On
• 0 = Off
• 1 = On
• 0 = Off
• 1 = On
Number of compressors
installed in the unit.
Compressor Heating source
capacity.
BAS-SVP18D-EN