Trane Tracer UC600 Integration Manual page 27

For packaged outdoor air unit
Table of Contents

Advertisement

Table 10. All object types sorted by object name (continued)
Object Type
Object Name
Compressor Stage 1
BV25
Request
Compressor Stage 1
MV21
Status
Compressor Stage 2
BV29
Request
Compressor Stage 2
MV22
Status
Compressor Stage 3
BV30
Request
Compressor Stage 3
MV7
Status
Compressor Stage 4
BV31
Request
Compressor Stage 4
MV8
Status
Condenser Coil
AV24
Temperature Setpoint
Condenser Fan
BO14
Command
Condenser Fan Speed
AO7
Command
Cooling Capacity
AV52
Cooling Lockout BAS
BV26
DAT High Temp Cutout
AV6
DAT Low Temp Cutout
AV15
DAT Temp Cutout Time
AV16
BV4
Defrost Mode
Dehumidification
BV27
Command
Dehumidification System
MV16
Status
Diagnostic: Discharge Air
BV6
Temperature Source
Failure
Diagnostic: Duct Static
BV36
Pressure Failure
Diagnostic: ERV Leaving
BV32
Air Conditions Failure
Diagnostic: Evap Temp
BV34
Source Failure
Diagnostic: Heat Failure
BV42
Diagnostic: OAD Proving
BV3
Switch
Diagnostic: Outdoor Air
BV14
Humidity Source Failure
BAS-SVP18D-EN
Min / Max
When the Point Exists
Units with 1+
Compressors.
Units with 1+
Compressors.
Units with 2+
Compressors.
Units with 2+
Compressors.
Units with 3+
Compressors.
Units with 3+
Compressors
Units with 4 Compressors.
Units with 4 Compressors
Units with Head Pressure
Control and isn't an Air
80 – 125 °F
Source Heat Pump.
Units with Sound
Attenuation Package or is
an Air Source Heat Pump.
Units with Head Pressure
0 - 100%
Control.
Units with DX Cooling.
0 - 100%
Units with DX Cooling.
90 – 130 °F
All Units.
35 – 50 °F
All Units.
10 - 25
All Units.
Units that are Heat Pump.
Units that are Space
Control, Single Zone
VAV, or Discharge Control.
All Units.
All Units.
Units that are Multi Zone
VAV.
Units that are Water
Source Heat Pump with an
ERV.
Units with DX Cooling.
Units with Gas as the
Primary Heat.
All Units.
All Units.
O O b b j j e e c c t t a a n n d d D D i i a a g g n n o o s s t t i i c c D D a a t t a a P P o o i i n n t t s s
Description
• 0 = Off
• 1 = On
• 1 = Off
• 2 = On
• 3 = Not Present
• 0 = Off
• 1 = On
• 1 = Off
• 2 = On
• 3 = Not Present
• 0 = Off
• 1 = On
• 1 = Off
• 2 = On
• 3 = Not Present
• 0 = Off
• 1 = On
• 1 = Off
• 2 = On
• 3 = Not Present
Temperature setpoint used to
modulate condenser fan(s).
• 0 = Off
• 1 = On
Analog condenser fan speed
command
Primary cooling source
capacity.
• 0 = Normal
• 1 = Lockout
If the discharge air
temperature is greater than
the discharge air high limit for
(AV16) minutes, the controller
signals an alarm
and shuts down the unit.
If the discharge air
temperature is less than the
discharge air low limit for
(AV16) minutes, the controller
signals an alarm and
shuts down the unit.
Time required for low limit or
high limit temperature to
signal alarm.
• 0 = Disabled
• 1 = Enabled
• 0 = Disabled
• 1 = Enabled
• 1 = Off
• 2 = On
• 3 = Not Present
Auto-Reset diagnostic.
• 0 = Normal
• 1 = Fail
Auto-Reset diagnostic.
• 0 = Normal
• 1 = Fail
Auto-Reset diagnostic.
• 0 = Normal
• 1 = Fail
Auto-Reset diagnostic.
• 0 = Normal
• 1 = Fail
Auto-Reset diagnostic.
• 0 = Normal
• 1 = Fail
Latching diagnostic. Cleared
with Alarm Reset.
• 0 = Normal
• 1 = Fail
Auto-Reset diagnostic.
• 0 = Normal
• 1 = Fail
27