Trane Tracer UC600 Integration Manual page 24

For packaged outdoor air unit
Table of Contents

Advertisement

O O b b j j e e c c t t a a n n d d D D i i a a g g n n o o s s t t i i c c D D a a t t a a P P o o i i n n t t s s
Table 8. Binary values
Object Type
Object Name
Diagnostic: Supply Fan
BV1
Failure
Diagnostic: Space
BV2
Temperature Setpoint
Failure
Diagnostic: OAD Proving
BV3
Switch
BV4
Defrost Mode
BV5
HGRH Purge Mode
Diagnostic: Discharge Air
BV6
Temperature Source
Failure
Auxiliary Heating Mode
BV7
BV9
Economizer Mode
Low Temp Lockout
BV10
Diagnostic: Space
BV11
Temperature
Source Failure
Diagnostic: Space
BV12
Humidity Source Failure
Diagnostic: Outdoor Air
BV13
Temperature Source
Failure
Diagnostic: Outdoor Air
BV14
Humidity Source Failure
High Temp Lockout
BV15
BV16
Alarm Reset
System LOCKOUT
BV17
Return Air Damper Option
BV18
Diagnostic: Space RH
BV19
Source Failure
Space
BV20
Temp/Humidity Sensor
Installed
BV21
Heat Cool Mode Active
Unoccupied Cooling Mode
BV22
BAS
Unoccupied Cooling Mode
BV23
24
When the Point
Min /Max
Exists
All Units.
Units with Thumbwheel
Installed.
All Units.
None/None
Units that are Heat
Pump.
Units with Hot Gas
Reheat.
All Units.
Units that are Heat
Pump.
Units with Modulating
Dampers.
All Units.
Units that are Space
Control or Single Zone
VAV.
Units that are Space
Control or Single Zone
VAV.
All Units.
All Units.
All Units.
None/None
All Units.
All Units.
All Units.
Units that are Space
Control or Single Zone
VAV.
Units that are Space
Control or Single Zone
VAV.
All Units.
All Units.
All Units.
Description
Latching diagnostic. Cleared
with Alarm Reset.
• 0 = Normal
• 1 = Fail
• 0 = Normal
• 1 = Fail
Latching diagnostic. Cleared
with Alarm Reset.
• 0 = Normal
• 1 = Fail
• 0 = Disabled
• 1 = Enabled
• 0 = Disabled
• 1 = Enabled
Auto-Reset diagnostic.
• 0 = Normal
• 1 = Fail
• 0 = Disabled
• 1 = Enabled
• 0 = Disabled
• 1 = Enabled
Latching diagnostic. Cleared
with Alarm Reset.
• 0 = Normal
• 1 = Fail
Auto-Reset diagnostic.
• 0 = Normal
• 1 = Fail
Auto-Reset diagnostic.
• 0 = Normal
• 1 = Fail
Auto-Reset diagnostic.
• 0 = Normal
• 1 = Fail
Auto-Reset diagnostic.
• 0 = Normal
• 1 = Fail
Latching diagnostic. Cleared
with Alarm Reset.
• 0 = Normal
• 1 = Fail
1 = Reset diagnostics or
lockouts. This will reset ALL
diagnostics or lockouts. If the
condition still exists, the
diagnostic reoccurs.
Latching diagnostic. Cleared
with Alarm Reset.
• 0 = Normal
• 1 = Fail
• 0 = Not Installed
• 1 = Installed
Auto-Reset diagnostic.
• 0 = Normal
• 1 = Fail
• 0 = Not Installed
• 1 = Installed
• 0 = Heat
• 1 = Cool
• 0 = Disabled
• 1 = Enabled
• 0 = Disabled
• 1 = Enabled
BAS-SVP18D-EN