Trane Tracer UC600 Integration Manual page 28

For packaged outdoor air unit
Table of Contents

Advertisement

O O b b j j e e c c t t a a n n d d D D i i a a g g n n o o s s t t i i c c D D a a t t a a P P o o i i n n t t s s
Table 10. All object types sorted by object name (continued)
Object Type
Object Name
Diagnostic: Outdoor Air
BV13
Temperature Source
Failure
Diagnostic: Space
BV12
Humidity Source Failure
Diagnostic: Space RH
BV19
Source Failure
Diagnostic: Space
BV2
Temperature Setpoint
Failure
Diagnostic: Space
BV11
Temperature Source
Failure
Diagnostic: Supply Fan
BV1
Failure
Discharge Air Cooling
AV30
Setpoint
Discharge Air Heating
AV32
Setpoint
Discharge Air
AV5
Temperature Active
Discharge Air
AV4
Temperature BAS
Discharge Air
AI11
Temperature Local
Discharge Air
AV68
Temperature Setpoint
Discharge Air
AV66
Temperature Setpoint
Active
Discharge Air
AV67
Temperature Setpoint
BAS
Duct Static Pressure
AV65
Active
AV64
Duct Static Pressure BAS
Duct Static Pressure
AI23
Local
Duct Static Pressure
AV49
Setpoint
Duct Static Pressure
AV53
Setpoint Active
Duct Static Pressure
AV46
Setpoint BAS
Economizer Control Type
BV45
BV9
Economizer Mode
ERV Bypass Position
AO6
Command
BO15
ERV Command
ERV Supply Side Leaving
AI17
Temperature Local
BI2
ESTOP
Evaporator Coil Leaving
AI15
Temperature Local
Evaporator Leaving
AV14
Temperature Setpoint
AV54
Exhaust Air Flow Active
Exhaust Air Flow
AV57
Setpoint
28
Min / Max
When the Point Exists
All Units.
Units that are Space
Control or Single Zone
VAV.
Units that are Space
Control or Single Zone
VAV.
Units with Thumbwheel
Installed.
Units that are Space
Control or Single Zone
VAV.
All Units.
Units with Discharge Air
47 – 90 °F
Control.
Units with Discharge Air
45 – 100 °F
Control.
-10 to 150
All Units.
°F
-10 to 150
All Units.
°F
-25 to 135
All Units.
°F
45 – 120 °F
Units with Multi Zone VAV.
38 -130 °F
Units with Multi Zone VAV.
45 – 90 °F
Units with Multi Zone VAV.
-6 to 6 in(H
O)
Units with Multi Zone VAV.
2
-6 to 6 in(H
O)
Units with Multi Zone VAV.
2
0 - 2 in(H
O)
Unit with Multizone VAV.
2
-1 to 6 in(H
O)
Units with Multi Zone VAV.
2
-1 to 6 in(H
O)
Unit with Multizone VAV.
2
-1 to 6 in(H
O)
Unit with Multizone VAV.
2
All Units.
Units with Modulating
Dampers.
0 - 100%
Units with ERV.
Units with an ERV.
Units with an ERV and is a
-58 to 482
Water Source Heat Pump.
°F
All Units.
-25 to 135
Units with Compressors.
°F
45 – 75 °F
All Units.
0 – 15000
Units with Piezo Ring on
cfm
the Exhaust Fan.
OAB or OAG units that are
208v or 460v, and does
0 – 7500
not have Modulating
cfm
Dampers with Exhaust
Fan(s).
Description
Auto-Reset diagnostic.
• 0 = Normal
• 1 = Fail
Auto-Reset diagnostic.
• 0 = Normal
• 1 = Fail
Auto-Reset diagnostic.
• 0 = Normal
• 1 = Fail
• 0 = Normal
• 1 = Fail
Auto-Reset diagnostic.
• 0 = Normal
• 1 = Fail
Latching diagnostic. Cleared
with Alarm Reset.
• 0 = Normal
• 1 = Fail
Discharge air setpoing during
cooling mode.
Discharge air setpoing during
heating mode.
Actively used discharge air
temperature.
Communicated discharge air
temperature.
Local discharge air
temperature sensor.
Discharge air temperature
setpoint.
Actively used discharge air
temperature setpoint.
Communicated discharge air
temperature setpoint.
Actively used duct static
pressure.
Communicated duct static
pressure.
Local supply duct pressure
sensor.
Setpoint used to modulate
indoor fan.
Actively used duct static
pressure setpoint.
Communicated duct static
pressure setpoint.
• 0 = Dry Bulb
• 1 = Dry Bulb and Enthalpy
• 0 = Disabled
• 1 = Enabled
Analog ERV bypass damper
command.
• 0 = Off
• 1 = On
Local temperature sensor
located post ERV on the supply
air side.
Normally Open Input. Auto-
Reset diagnostic.
• 0 = Normal
• 1 = ESTOP
Local evaporator leaving air
temperature sensor.
Evaporator leaving air
temperature setpoint during
dehumidification mode or
Single Zone VAV
The amount of air delivered by
the exhaust fan.
Setpoint used to modulate
exhaust fan speed.
BAS-SVP18D-EN