Trane Tracer UC600 Integration Manual page 21

For packaged outdoor air unit
Table of Contents

Advertisement

Table 5. Analog values (continued)
Object Type
Object Name
DAT Temp Cutout Time
AV16
IVFD Signal
AV17
Compressor Heating
AV18
Capacity
Space Temperature BAS
AV20
Space Temperature
AV23
Active
Condenser Coil
AV24
Temperature Setpoint
Space Temperature
AV25
Setpoint BAS
Unoccupied Cooling
AV26
Setpoint
Unoccupied Heating
AV27
Setpoint
Unoccupied Dewpoint
AV28
Setpoint
Outdoor Air Cooling
AV29
Setpoint (OACS)
Discharge Air Cooling
AV30
Setpoint
Compressor Count
AV31
Discharge Air Heating
AV32
Setpoint
Outdoor Air Heating
AV33
Setpoint (OAHS)
Space Dewpoint
AV34
Setpoint (SPDS)
Space Dewpoint Active
AV35
Minimum Discharge Air
AV36
Cooling Setpoint
Space Temperature
AV37
Setpoint Active
AV38
Outdoor Air Flow Active
Supply Air Flow Setpoint
AV39
PEVFD Setpoint
AV40
Supply Air Flow Active
AV41
Minimum Discharge Air
AV43
Heating Setpoint
Heat Capacity
AV44
Maximum Supply Air
AV45
Temperature
Duct Static Pressure
AV46
Setpoint BAS
Maximum OA Damper
AV47
Position
BAS-SVP18D-EN
Min / Max
When the Point Exists
10 - 25
All Units.
When Unit is an OAD, OAK,
50 - 100%
or OAN and the Supply Fan
is CV.
Units that are Air Source
or Water Source Heat
0 – 100%
Pumps.
-58 to 482 °F
All Units.
-58 to 482 °F
All Units.
Units with Head Pressure
Control and isn't an Air
80 to 125 °F
Source Heat Pump.
Units that are Space
-58 to 482 °F
Control or Single Zone
VAV.
Units with Space
60 to 90 °F
Temperature/Humidity
Sensor Installed.
Units with Space
45 to 90 °F
Temperature/Humidity
Sensor Installed.
Units with Space
49 to 100 °F
Temperature/Humidity
Sensor Installed.
Units with Space Control,
Discharge Control, or
60 – 90 °F
Single Zone VAV.
Units with Discharge Air
47 – 90 °F
Control.
Units with DX Cooling.
0 - 4
Units with Discharge Air
45 – 100 °F
Control.
Units with Space Control,
Discharge Control, or
40 – 75 °F
Single Zone VAV.
Units with Space Control,
Discharge Control, or
-10 – 150 °F
Single Zone VAV.
-58 to 482 °F
All Units.
Units that are Space
40 – 65 °F
Control.
Units that are Space
45 – 95 °F
Control or Single Zone
VAV.
Units with Outside Air Flow
0 – 13500 cfm
Monitoring.
OAB or OAG units that are
0 – 7500 cfm
208v or 460v.
OAD, OAK, or OAN that
does NOT have Modulating
0 – 100 %
Dampers or Powered
Exhaust.
Units with Piezo Ring on
0 – 15000 cfm
Supply Fan.
Units that are Space
40 - 65 °F
Control.
Units with Primary Heat.
0 – 100 %
All Units with Primary Heat
80 – 120 °F
or Heat Pumps
-1 to 6 in(H
O)
Unit with Multizone VAV.
2
Units with Modulating
0 – 100 %
Dampers.
O O b b j j e e c c t t a a n n d d D D i i a a g g n n o o s s t t i i c c D D a a t t a a P P o o i i n n t t s s
Description
Time required for low limit or
high limit temperature to
signal alarm.
Supply fan speed setpoint.
Compressor Heating source
capacity.
Communicated space
temperature.
Actively used space
temperature.
Temperature setpoint used to
modulate condenser fan(s).
Communicated space
temperature setpoint.
Space cooling setpoint used in
unoccupied mode.
Space heating setpoint used in
unoccupied mode.
If the space dewpoint rises
above this setpoint during
unoccupied mode then
dehumidification will be
enabled.
Setpoint used to enable
cooling.
Discharge air setpoint during
cooling mode.
Number of compressors
installed in the unit.
Discharge air setpoing during
heating mode.
Setpoint used to enable
heating.
If the outdoor air dewpoint is
greater than OADS, the unit
will enable dehumidification.
Actively used space dewpoint.
Cooling capacity is limited in
order to not fall below this
temperature.
Actively used space
temperature setpoint.
Actively used outside air flow.
Setpoint used to modulate the
indoor fan speed.
Fan speed setpoint used to
control the indoor fan speed.
Actively used supply airflow.
Primary or Compressor
Heating Capacity is limited in
order to not fall below this
temperature.
Primary heating source
capacity.
Primary or Compressor
Heating Capacity is limited in
order to not exceed this
temperature.
Communicated duct static
pressure setpoint.
Maximum outdoor air damper
position.
21