Table 10. All object types sorted by object name (continued)
Object Type
Object Name
Exhaust Damper
BO9
Actuators
Exhaust Damper
BI7
Endswitch
Exhaust Fan Pressure
AI9
Local
Exhaust Leaving
AI13
Temperature Local
BI3
Filter Status
BI6
Gas Valve Status
BO3
Heat 1 Command
BO7
Heat 2 Command
BO8
Heat 3 Command
Heat Capacity
AV44
BV21
Heat Cool Mode Active
MV4
Heat Cool Mode Status
Heat Type
MV9
Heat/Cool Mode
AV69
Deadband
Heating Output
AO11
Command
AO1
HGRH Command
HGRH Purge Mode
BV5
High Temp Lockout
BV15
BO4
Inducer Command
AO2
IVFD Command
IVFD Signal
AV17
Liquid Line Pressure
AV12
Setpoint
Low Temp Lockout
BV10
Maximum OA Damper
AV47
Position
Maximum Supply Air
AV70
Flow Setpoint
BAS-SVP18D-EN
Min / Max
When the Point Exists
Units with Isolation
Dampers.
Units with Isolation
Dampers.
Units with Piezo Ring on
0 - 25 in(H
O)
2
Exhaust Fan.
-25 to 135
Units with an ERV.
°F
All Units.
Units with Gas as the
Primary Heat.
Units with Primary Heat.
Units with Gas as the
Primary Heat and is a Split
Manifold Burner.
Units with Gas as the
Primary Heat and has Two
Heaters.
Units with Primary Heat.
0 – 100%
All Units.
All Units
All Units
-58 to 482
Units with Multi Zone VAV.
°F
Units with any type of
0 – 100%
Primary Heat.
Units with Modulating Hot
0 - 100%
Gas Reheat.
Units with Hot Gas
Reheat.
All Units.
Units with Gas as the
Primary Heat.
0 - 100%
All Units.
When Unit is an OAD,
OAK, or OAN and the
50 - 100%
Supply Fan is CV.
Air Source Heat Pumps
200 – 600
with Head Pressure
psi
Control.
All Units.
Units with Modulating
0 - 100%
Dampers.
350 –
Units with Single Zone or
13500 cfm
Multi Zone VAV.
O O b b j j e e c c t t a a n n d d D D i i a a g g n n o o s s t t i i c c D D a a t t a a P P o o i i n n t t s s
Description
• 0 = Off
• 1 = On
Normally open input.
• 0 = Not Proven
• 1 = Proven
Local exhaust fan piezo ring
pressure.
Local exhaust leaving
temperature sensor
Normally open input.
• 0 = Clean
• 1 = Clogged
Normally open input.
• 0 = Off
• 1 = On
• 0 = Off
• 1 = On
• 0 = Off
• 1 = On
• 0 = Off
• 1 = On
Primary heating source
capacity.
• 0 = Heat
• 1 = Cool
• 1 = Auto
• 2 = Heat
• 3 = Morning Warm-up
• 4 = Cool
• 5 = Night Purge
• 6 = Pre Cool
• 7 = Off
• 1 = No Heat
• 2 = Indirect Fired Gas Heat
• 3 = Electric Heat
• 4 = Other
• 5 = Direct Fired Gas Heat
• 6 = Hot Water/Steam
Heat is enabled when Outdoor
Air Temperature drops below
Discharge Temperature
Setpoint - Heat/Cool Mode
Deadband. Cooling is enabled
when Outdoor Air temperature
rises above the Discharge
Temperature Setpoint.
Analog heating output
command.
Analog HGRH output
command.
• 0 = Disabled
• 1 = Enabled
Latching diagnostic. Cleared
with Alarm Reset.
• 0 = Normal
• 1 = Fail
• 0 = Off
• 1 = On
Analog supply fan VFD speed.
Supply fan speed setpoint.
Pressure setpoint used to
modulate condenser fan(s).
Latching diagnostic. Cleared
with Alarm Reset.
• 0 = Normal
• 1 = Fail
Maximum outdoor air damper
position.
Supply air flow is limited to not
exceed this number.
29