Table 8. Binary values (continued)
Object Type
Object Name
Compressor Stage 1
BV25
Request
Cooling Lockout BAS
BV26
Dehumidification
BV27
Command
BV28
Thumbwheel Installed
Compressor Stage 2
BV29
Request
Compressor Stage 3
BV30
Request
Compressor Stage 4
BV31
Request
Diagnostic: ERV Leaving
BV32
Air Conditions Failure
Pre-Purge Status
BV33
Diagnostic: Evap Temp
BV34
Source Failure
Y1 Space Lockout
BV35
Diagnostic: Duct Static
BV36
Pressure Failure
Unoccupied Dehumid
BV37
Mode BAS
Unoccupied Heating Mode
BV38
BAS
Unoccupied Heating Mode
BV39
Unoccupied Dehumid
BV40
Mode
Diagnostic: Heat Failure
BV42
BV43
Ventilation
Economizer Control Type
BV45
Table 9. Multi-state values
Object Type
Object Name
Occupancy Request
MV1
Occupancy Status
MV2
MV4
Heat Cool Mode Status
Compressor Stage 3
MV7
Status
Compressor Stage 4
MV8
Status
BAS-SVP18D-EN
When the Point
Min /Max
Exists
Units with 1+
Compressors.
Units with DX Cooling.
Units that are Space
Control, Single Zone
VAV, or Discharge
Control.
All Units.
Units with 2+
Compressors.
Units with 3+
Compressors.
Units with 4
Compressors.
Units that are Water
None/None
Source Heat Pump with
an ERV.
Units with Gas as the
Primary Heat.
Units with DX Cooling.
Units that are Space
Control or Single
Zone VAV.
Units that are Multi Zone
VAV.
All Units.
All Units.
All Units.
All Units.
Units with Gas as the
Primary Heat.
Units that are Space
Control, Single Zone VAV,
or Discharge Control.
All Units.
When the Point
Min / Max
Exists
All Units.
All Units.
None/None
All Units
Units with 3+
Compressors
Units with 4 Compressors
O O b b j j e e c c t t a a n n d d D D i i a a g g n n o o s s t t i i c c D D a a t t a a P P o o i i n n t t s s
Description
• 0 = Off
• 1 = On
• 0 = Normal
• 1 = Lockout
• 0 = Disabled
• 1 = Enabled
• 0 = Not Installed
• 1 = Installed
• 0 = Off
• 1 = On
• 0 = Off
• 1 = On
• 0 = Off
• 1 = On
Auto-Reset diagnostic.
• 0 = Normal
• 1 = Fail
• 0 = Disabled
• 1 = Enabled
Auto-Reset diagnostic.
• 0 = Normal
• 1 = Fail
• 0 = Disabled
• 1 = Enabled
Auto-Reset diagnostic.
• 0 = Normal
• 1 = Fail
• 0 = Disabled
• 1 = Enabled
• 0 = Disabled
• 1 = Enabled
• 0 = Disabled
• 1 = Enabled
• 0 = Disabled
• 1 = Enabled
Auto-Reset diagnostic.
• 0 = Normal
• 1 = Fail
• 0 = Disabled
• 1 = Enabled
• 0 = Dry Bulb
• 1 = Dry Bulb and Enthalpy
Description
• 1 = Occupied
• 2 = Unoccupied
• 3 = Occupied Bypass
• 4 = Occupied Standby
• 5 = Auto
• 1 = Occupied
• 2 = Unoccupied
• 3 = Occupied Bypass
• 4 = Occupied Standby
• 5 = Unknown
• 1 = Auto
• 2 = Heat
• 3 = Morning Warm-up
• 4 = Cool
• 5 = Night Purge
• 6 = Pre Cool
• 7 = Off
• 1 = Off
• 2 = On
• 3 = Not Present
• 1 = Off
• 2 = On
• 3 = Not Present
25