Table 2. Descriptions and configurations (continued)
Required Properties
Object Type
Read
Analog Value
• Object_Identifier
• Object_Name
• Object_Type
• Present_Value
• Status_Flags
• Event_State
• Out_Of_Service
• Units
Binary Input
• Object_Identifier
• Object_Name
• Object_Type
• Present_Value
• Status_Flags
• Event_State
• Out_Of_Service
• Polarity
Binary Output • Object_Identifier
• Object_Name
• Object_Type
• Present_Value
• Status_Flags
• Event_State
• Out_Of_Service
• Polarity
• Priority_Array
• Relinquish_Default
BAS-SVP18D-EN
B B A A C C n n e e t t D D a a t t a a P P o o i i n n t t s s a a n n d d C C o o n n f f i i g g u u r r a a t t i i o o n n P P r r o o p p e e r r t t y y D D e e f f i i n n i i t t i i o o n n s s
Optional Properties
Properties Written
• Object_Name
• Description
• Reliability
• Description
• Out_Of_Service
• Priority_Array
• Present_Value
• Relinquish_Default
• Reliability
• COV_Increment
• Relinquish_Default
• Time_Delay
• Notification_Class
• COV_Increment
• Time_Delay
• High_Limit
• Notification_Class
• Low_Limit
• Deadband
• High_Limit
• Low_Limit
• Limit_Enable
• Event_Enable
• Deadband
• Limit_Enable
• Acked_Transitions
• Event_Enable
• Notify_Type
• Event_Time_Stamps
• Notify_Type
• Description
• Object_Name
• Description
• Inactive_Text
• Out_Of_Service
• Active_Text
• Change_Of_State_Time
• Inactive_Text
• Active_Text
• Change_Of_State_Count
• Time_Of_State_Count_
• Present_Value
• Reliability
Reset
• Change_Of_State_
• Elapsed_Active_Time
Count
• Time_Of_Active_Time_
• Elapsed_Active_Time
Reset
• Time_Delay
• Time_Delay
• Notification_Class
• Notification_Class
• Alarm_Value
• Alarm_Value
• Event_Enable
• Event_Enable
• Polarity
• Acked_Transitions
• Notify_Type
• Notify_Type
• Event_Time_Stamps
• Reliability
• Object_Name
• Description
• Inactive_Text
• Description
• Out_Of_Service
• Active_Text
• Change_Of_State_Time
• Inactive_Text
• Active_Text
• Change_Of_State_Count
• Present_Value
• Time_Of_State_Count_
Reset
• Reliability
• Change_Of_State_
• Elapsed_Active_Time
• Time_Of_Active_Time_
Count
• Elapsed_Active_Time
Reset
• Minimum_On_Time
• Minimum_On_Time
• Minimum_Off_Time
• Minimum_Off_Time
• Relinquish_Default
• Priority_Array
• Time_Delay
• Time_Delay
• Notification_Class
• Notification_Class
• Event_Enable
• Feedback_Value
• Notify_Type
• Event_Enable
• Acked_Transitions
• Notify_Type
• Event_Time_Stamps
• Reliability
Ability to
Ability to Delete
Read
Create
Yes
Yes, user create
objects only
Yes
Yes, user create
objects only
Yes
Yes, user create
objects only
15