Trane Tracer UC600 Integration Manual page 20

For packaged outdoor air unit
Table of Contents

Advertisement

O O b b j j e e c c t t a a n n d d D D i i a a g g n n o o s s t t i i c c D D a a t t a a P P o o i i n n t t s s
Table 4. Analog outputs (continued)
Object Type
Object Name
Circuit 1 Digital Scroll/
AO3
Variable Speed
Command
AO4
PEVFD Command
AO5
OAD Position Command
ERV Bypass Position
AO6
Command
Condenser Fan Speed
AO7
Command
Circuit 2 Digital Scroll/
AO8
Variable Speed
Command
Heating Output
AO11
Command
Table 5. Analog values
Object Type
Object Name
Occupied Cooling
AV1
Setpoint
Occupied Heating
AV2
Setpoint
Occupied Offset
AV3
Discharge Air
AV4
Temperature BAS
Discharge Air
AV5
Temperature Active
DAT High Temp Cutout
AV6
Space RH Active
AV7
Space RH BAS
AV8
Occupied Bypass Time
AV9
Outdoor Air Dewpoint
AV10
Setpoint (OADS)
Outdoor Air Dewpoint
AV11
Active
Liquid Line Pressure
AV12
Setpoint
Outdoor Air Minimum
AV13
Flow Setpoint BAS
Evaporator Leaving
AV14
Temperature Setpoint
DAT Low Temp Cutout
AV15
20
Min / Max
When the Point Exists
Units with Digital Scroll or
0 - 100%
Variable Speed on the first
circuit.
Units with Powered
0 - 100%
Exhaust.
Units with Modulating
0 - 100%
Dampers.
0 - 100%
Units with ERV.
Units with Head Pressure
0 - 100%
Control.
Units with Digital Scroll or
0 - 100%
Variable Speed on the
second circuit.
Units with any type of
0 - 100%
Primary Heat.
Min / Max
When the Point Exists
Units with Space Control
55 – 85 °F
or Single Zone VAV.
Units with Space Control
55 – 85 °F
or Single Zone VAV.
0.5 – 30 Δ °F
All Units.
-10 to 150 °F
All Units.
-10 to 150 °F
All Units.
90 – 130 °F
All Units.
Units with Space Humidity
-150 to 150%
Sensor Installed.
-150 to 150%
All Units.
Units with Thumbwheel
2 - 360
Installed.
Units with Space Control,
Discharge Control, or
49 – 100 °F
Single Zone VAV.
-10 to 150 °F
All Units.
Air Source Heat Pumps
200 – 600 psi
with Head Pressure
Control.
VAV Units with Outdoor air
flow Monitoring and
0 – 13500 cfm
Modulating Dampers.
45 – 75 °F
All Units.
35 – 50 °F
All Units.
Description
Analog digital scroll or variable
speed output command.
Analog exhaust fan VFD
speed.
Analog outdoor air damper
command.
Analog ERV bypass damper
command.
Analog condenser fan speed
command
Analog digital scroll or variable
speed output command.
Analog heating output
command.
Description
Space cooling setpoint used in
occupied mode.
Space heating setpoint used in
occupied mode.
The value used to calculate the
heating/cooling setpoints in
occupied mode. If the unit has
a thumbwheel installed
Occupied Offset defaults to 2.
• Active heating setpoint =
active setpoint – occupied
offset.
• Active cooling setpoint =
active setpoint + occupied
offset.
Communicated discharge air
temperature.
Actively used discharge air
temperature.
If the discharge air
temperature is greater than
the discharge air high limit for
(AV16) minutes, the controller
signals an alarm and shuts
down the unit.
Actively used space relative
humidity.
Communicated space relative
humidity.
Time that Unoccupied Mode is
delayed when Occupied Button
is pressed.
If the outdoor air dewpoint is
greater than OADS, the unit
will enable dehumidification.
Dewpoint of the outdoor air.
This point is calculated within
the program.
Pressure setpoint used to
modulate condenser fan(s).
air flow setpoint used to
modulate dampers.
Evaporator leaving air
temperature setpoint during
dehumidification mode or
Single Zone VAV
If the discharge air
temperature is less than the
discharge air low limit for
(AV16) minutes, the controller
signals an alarm and shuts
down the unit.
BAS-SVP18D-EN