Trane Tracer UC600 Integration Manual page 23

For packaged outdoor air unit
Table of Contents

Advertisement

Table 6. Binary inputs
Object Type
Object Name
Supply Fan Status
BI1
BI2
ESTOP
BI3
Filter Status
Occupancy Input
BI4
OA Damper End Switch
BI5
BI6
Gas Valve Status
Exhaust Damper
BI7
Endswitch
BI8
Water Flow
Water Coil Low Temp
BI9
Switch
Table 7. Binary outputs
Object Type
Object Name
Supply Fan Start Stop
BO1
Command
Outdoor Air Damper
BO2
Command
BO3
Heat 1 Command
BO4
Inducer Command
Compressor 3 Command
BO5
Compressor 4 Command
BO6
BO7
Heat 2 Command
BO8
Heat 3 Command
Exhaust Damper
BO9
Actuators
BO10
Powered Exhaust Enable
Compressor 1 Command
BO11
Compressor 2 Command
BO12
BO13
Pre-Heat Enable
BO14
Condenser Fan Command
BO15
ERV Command
Circuit 1 Reversing Valve
BO16
Circuit 2 Reversing Valve
BO17
BAS-SVP18D-EN
When the Point
Min / Max
Exists
All Units.
All Units.
All Units.
All Units.
None/None
All Units.
Units with Gas as the
Primary Heat.
Units with Isolation
Dampers.
Units that are Water
Source Heat Pump.
Units that are Water
Source Heat Pump.
When the Point
Min /Max
Exists
All Units.
All Units.
Units with Primary Heat.
Units with Gas as the
Primary Heat.
Units with 3+
Compressors.
Units with 4+
Compressors.
Units with Gas as the
Primary Heat and is a
Split Manifold Burner.
Units with Gas as the
Primary Heat and has
Two Heaters.
Units with Isolation
None/None
Dampers.
Units with Isolation
Dampers or has Dual
Point Power.
Units with 1+
Compressors.
Units with 2+
Compressors.
Units with Pre-Heat.
Units with Sound
Attenuation Package or
an Air Source Heat Pump.
Units with an ERV.
Units that are Heat
Pump.
Units that are Heat Pump
and Two Circuits.
O O b b j j e e c c t t a a n n d d D D i i a a g g n n o o s s t t i i c c D D a a t t a a P P o o i i n n t t s s
Description
Normally Closed Input
• 0 = On
• 1 = Off
Normally Open Input. Auto-
Reset diagnostic.
• 0 = Normal
• 1 = ESTOP
Normally open input.
• 0 = Clean
• 1 = Clogged
Normally open input.
• 0 = Unoccupied
• 1 = Occupied
Normally open input.
• 0 = Not Proven
• 1 = Proven
Normally open input.
• 0 = Off
• 1 = On
Normally open input.
• 0 = Not Proven
• 1 = Proven
Normally open input.
• 0 = Off
• 1 = On
Normally closed input.
• 0 = Open
• 1 = Closed
Description
• 0 = Off
• 1 = On
• 0 = Open
• 1 = Closed
• 0 = Off
• 1 = On
• 0 = Off
• 1 = On
• 0 = Off
• 1 = On
• 0 = Off
• 1 = On
• 0 = Off
• 1 = On
• 0 = Off
• 1 = On
• 0 = Off
• 1 = On
• 0 = Off
• 1 = On
• 0 = Off
• 1 = On
• 0 = Off
• 1 = On
• 0 = Off
• 1 = On
• 0 = Off
• 1 = On
• 0 = Off
• 1 = On
• 0 = Off
• 1 = On
• 0 = Off
• 1 = On
23