Trane Tracer UC600 Integration Manual page 30

For packaged outdoor air unit
Table of Contents

Advertisement

O O b b j j e e c c t t a a n n d d D D i i a a g g n n o o s s t t i i c c D D a a t t a a P P o o i i n n t t s s
Table 10. All object types sorted by object name (continued)
Object Type
Object Name
Maximum Supply Air
AV45
Temperature
Minimum Discharge Air
AV36
Cooling Setpoint
Minimum Discharge Air
AV43
Heating Setpoint
Minimum OA Damper
AV48
Position
Minimum Supply Air Flow
AV59
Setpoint
OA Damper End Switch
BI5
AO5
OAD Position Command
AI7
OAD Position Local
Occupancy Input
BI4
Occupancy Request
MV1
Occupancy Status
MV2
Occupied Bypass Time
AV9
Occupied Cooling
AV1
Setpoint
Occupied Heating
AV2
Setpoint
Occupied Offset
AV3
Outdoor Air Cooling
AV29
Setpoint (OACS)
Outdoor Air Damper
BO2
Command
Outdoor Air Dewpoint
AV11
Active
Outdoor Air Dewpoint
AV10
Setpoint (OADS)
AV38
Outdoor Air Flow Active
AI10
Outdoor Air Flow Local
Outdoor Air Heating
AV33
Setpoint (OAHS)
Outdoor Air Humidity
AV82
Active
30
Min / Max
When the Point Exists
All Units with Primary
80 – 120
Heat or Heat Pumps
°F
Units that are Space
40 – 65 °F
Control.
Units that are Space
40 – 65 °F
Control.
Units with Modulating
0 - 100%
Dampers.
300 –
Units with Single Zone or
13500 cfm
Multi Zone VAV.
All Units.
Units with Modulating
0 - 100%
Dampers.
Units with Modulating
0 - 100%
Dampers.
All Units.
All Units.
All Units.
Units with Thumbwheel
2 - 360
Installed.
Units with Space Control
55 – 85 °F
or Single Zone VAV.
Units with Space Control
55 – 85 °F
or Single Zone VAV.
0.5 – 30 Δ
All Units.
°F
Units with Space Control,
Discharge Control, or
60 – 90 °F
Single Zone
VAV.
All Units.
-10 to 150
All Units.
°F
Units with Space Control,
49 – 100
Discharge Control, or
°F
Single Zone VAV.
Units with Outside Air
0 - 13500
Flow Monitoring.
cfm
Units with Outside air flow
0 - 15000
Monitoring.
cfm
Units with Space Control,
Discharge Control, or
40 – 75 °F
Single Zone VAV.
0 – 100%
All Units.
Description
Primary or Compressor
Heating Capacity is limited in
order to not exceed this
temperature.
Cooling capacity is limited in
order to not fall below this
temperature.
Primary or Compressor
Heating
Capacity is limited in order to
not fall below this
temperature.
Minimum outdoor air damper
position.
Supply air flow is limited to not
fall below this number.
Normally open input.
• 0 = Not Proven
• 1 = Proven
Analog outdoor air damper
command.
Local outside air damper
position.
Normally open input.
• 0 = Unoccupied
• 1 = Occupied
• 1 = Occupied
• 2 = Unoccupied
• 3 = Occupied Bypass
• 4 = Occupied Standby
• 5 = Auto
• 1 = Occupied
• 2 = Unoccupied
• 3 = Occupied Bypass
• 4 = Occupied Standby
• 5 = Unknown
Time that Unoccupied Mode is
delayed when Occupied Button
is pressed.
Space cooling setpoint used in
occupied mode.
Space heating setpoint used in
occupied mode.
The value used to calculate the
heating/cooling setpoints in
occupied mode. If the unit has
a thumbwheel installed
Occupied Offset defaults to 2.
Active heating setpoint =
active setpoint – occupied
offset.
Active cooling setpoint =
active setpoint + occupied
offset.
Setpoint used to enable
cooling.
• 0 = Open
• 1 = Closed
Dewpoint of the outdoor air.
This point is calculated within
the program.
If the outdoor air dewpoint is
greater than OADS, the unit
will enable dehumidification.
Actively used outside air flow.
Local outside air flow.
Setpoint used to enable
heating.
Actively used outdoor air
relative humidity.
BAS-SVP18D-EN