Siemens SIPROTEC 5 6MU85 Manual page 96

Advertisement

12.34
Arc Protection
Setting Values
Threshold I>
Threshold 3I0>>
External trip initiation
Operating mode
Sensor
Threshold light
Channel
Dropout
The larger dropout differential (= | pickup threshold – dropout threshold |) of the following 2
criteria is used:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 90 % applies to the current threshold values.
Minimum absolute dropout differential
Protection-class current transformers
Instrument transformers
Times
Shortest operate time
Operating mode = light only
Shortest operate time
Operating mode = Current and light
76
OOT (Output Operating Time): Additional delay of the output medium used, for example, 5 ms with fast relay, see chapter
12.1.4 Relay Outputs
SIPROTEC 5, Merging Unit 6MU85, Manual
C53000-G5040-C074-1, Edition 01.2020
1 A @ 100 Irated
5 A @ 100 Irated
1 A @ 1.6 Irated
5 A @ 1.6 Irated
1 A @ 100 Irated
5 A @ 100 Irated
1 A @ 1.6 Irated
5 A @ 1.6 Irated
0.030 A to 35.000 A
0.15 A to 175.00 A
0.001 A to 1.600 A
0.005 A to 8.000 A
0.030 A to 35.000 A
0.15 A to 175.00 A
0.001 A to 1.600 A
0.005 A to 8.000 A
no
current
light
light only
current and light
point sensor
line sensor
custom
-28.00 dB to 0.00 dB
Possible settings, application-dependent
15 mA sec. (I
= 1 A) or
rated
75 mA sec. (I
= 5 A)
rated
0.5 mA sec. (I
= 1 A) or
rated
2.5 mA sec. (I
= 5 A)
rated
76
Approx. 2.6 ms + OOT
Approx. 4.0 ms + OOT at 50 Hz
Approx. 3.8 ms + OOT at 60 Hz
Technical Data
12.34 Arc Protection
Increments of 0.001 A
Increments of 0.01 A
Increments of 0.001 A
Increments of 0.001 A
Increments of 0.001 A
Increments of 0.01 A
Increments of 0.001 A
Increments of 0.001 A
Increments of 0.01