Technical Data
12.38 CFC
12.38
CFC
In order to estimate the tick consumption of a CFC chart, you can use the following formula:
T
= 5 ∙ n
Chart
where:
n
Number of indications routed as input in the CFC chart
Inp
n
Number of indications routed as output in the CFC chart
Outp
T
101 Ticks in Fast Event-Triggered level
TLev
104 Ticks in Event-Triggered level
54 Ticks in Measurement level
74 Ticks in Interlocking level
T
Number of internal connections between 2 CFC blocks in one chart
int
T
Used ticks per CFC block (see
Block
Table 12-4
Element
ABS_D
ABS_R
ACOS_R
ADD_D4
ADD_R4
ADD_XMV
ALARM
AND_SPS
AND10
APC_DEF
APC_EXE
APC_INFO
ASIN_R
ATAN_R
BLINK
BOOL_CNT
BOOL_INT
BSC_DEF
BSC_EXE
BSC_INFO
BUILD_ACD
BUILD_ACT
BUILD_BSC
BUILD_CMV
BUILD_DEL
BUILD_DPS
BUILD_ENS
BUILD_INS
BUILD_Q
BUILD_SPS
878
+ 5 ∙ n
+ T
+ ∑
T
Inp
Outp
TLev
i
int
Table
Ticks of the Individual CFC Blocks
+ ∑
T
j
Block
12-4)
Ticks
2.3
1.5
6.9
3.4
3.3
6.4
1.8
1.1
2.9
1.2
1.0
3.9
1.3
1.2
1.3
2.0
1.5
1.3
1.1
2.7
2.9
2.2
1.2
2.3
2.1
1.4
1.3
0.5
0.8
0.6
SIPROTEC 5, Merging Unit 6MU85, Manual
C53000-G5040-C074-1, Edition 01.2020