Technical Data
12.31 Analog-Units Function Group
12.31
Analog-Units Function Group
20-mA Unit Ether. 7XV5674-0KK00-1AA1
Max. number of connected 20-mA units
Max. number of channels per 20-mA unit
20-mA Unit Serial 7XV5674-0KK30-1AA1 (RS485) and 7XV5674-0KK40-1AA1 (Fiberglass)
Max. number of connected 20-mA units
Max. number of channels per 20-mA unit
RTD Unit (Ziehl TR1200) 7XV5662-6AD10
Max. number of connected RTD units
Max. number of sensors per RTD unit
Sensor type
RTD Unit (Ziehl TR1200 IP) 7XV5662-8AD10
Max. number of connected RTD units
Max. number of sensors per RTD unit
Sensor type
Temperature Measured Values
Unit of measurement for temperature
Pt 100
Ni 100
Ni 120
Resolution
Tolerance
870
4
12
4
12
4
12
Pt 100 to EN 60751; connection of Ni 100 and Ni 120
sensors possible. The measured values must be
converted in the evaluation unit.
4
12
Pt 100 to EN 60751; connection of Ni 100 and Ni 120
sensors possible. The measured values must be
converted in the evaluation unit.
°C or °F, adjustable
-199 °C to 800 °C (-326 °F to 1472 °F)
-54 °C to 278 °C (-65 °F to 532 °F)
-52 °C to 263 °C (-62 °F to 505 °F)
1 °C or 1 °F
±0.5 % of the measured value ±1 K
SIPROTEC 5, Merging Unit 6MU85, Manual
C53000-G5040-C074-1, Edition 01.2020

Advertisement