Download Print this page

Siemens SIPROTEC 5 6MU85 Manual page 95

Advertisement

Technical Data
12.33 Measuring Transducers
12.33
Measuring Transducers
Current Inputs
Value
Rated current measuring range
Maximum current measuring range
Tolerances
without trimming
with offset trimming
with full trimming
Sampling rate
Number of channels per measuring transducer
module
Analog-digital converter
872
Setting Range
± 20 mA
± 24 mA
± 124 μA (0.62 % at 20 mA)
± 60 μA (0.3 % at 20 mA)
± 20 μA (0.1% at 20 mA)
≥ 3 Hz
2 or 4
16 Bit Sigma/Delta
SIPROTEC 5, Merging Unit 6MU85, Manual
C53000-G5040-C074-1, Edition 01.2020

Advertisement