Download Print this page

Siemens SIPROTEC 5 6MU85 Manual page 79

Advertisement

Technical Data
12.20 Voltage-Sum Supervision
12.20
Voltage-Sum Supervision
Setting Values
Threshold
Delay failure indication
Dropout Ratio
Dropout ratio
Times
Tripping time
Dropout time
856
0.300 V to 170.000 V
0.00 s to 100.00 s
Increments of 0.001 V
Increments of 0.01 s
Approx. 0.97
Approx. 500 ms
Approx. 500 ms