Siemens SIPROTEC 5 6MU85 Manual page 56

Advertisement

12.10
Voltage Protection
Overvoltage Protection with 3-Phase Voltage
12.10.1
Setting Values for the Function
Stabilization counter
Setting Values for Stage Type Definite-Time Overvoltage Protection
Measured value
Method of measurement
Pickup mode
55
Pickup value
Time delay
Dropout ratio
Setting Values for Stage Type Inverse-Time Overvoltage Protection
Measured value
Method of measurement
Pickup mode
Pickup value
Pickup factor
Characteristic constant k
Characteristic constant α
Characteristic constant c
Time multiplier
Additional time delay
Reset time
Operate Curve for Stage Type Inverse-Time Overvoltage Protection
Where
T
Operate delay
op
T
Inverse-time delay
inv
T
Additional time delay (parameter Additional time delay)
add
55
If you have selected the method of measurement = RMS value, do not set the threshold value under 10 V.
SIPROTEC 5, Merging Unit 6MU85, Manual
C53000-G5040-C074-1, Edition 01.2020
0 to 10
Phase-to-phase
Phase-to-ground
Fundamental component
RMS value
1 out of 3
3 out of 3
0.300 V to 340.000 V
0.00 s to 300.00 s
0.90 to 0.99
Phase-to-phase
Phase-to-ground
Fundamental component
RMS value
1 out of 3
3 out of 3
0.300 V to 340.000 V
1.00 to 1.20
0.00 to 300.00
0.010 to 5.000
0.000 to 5.000
0.05 to 15.00
0.00 s to 60.00 s
0.00 s to 60.00 s
Technical Data
12.10 Voltage Protection
Increments of 1
Increments of 0.001 V
Increments of 0.01 s
Increments of 0.01
Increments of 0.001 V
Increments of 0.01
Increments of 0.01
Increments of 0.001
Increments of 0.001
Increments of 0.01
Increments of 0.01 s
Increments of 0.01 s
833