Time delay
Pickup delay
Dropout ratio
V< faulty ph-gnd vltg.
V> healthy ph-gnd. vltg.
Dropout
The greater dropout differential (= | pickup value – dropout value |) of the following 2 criteria
applies:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for the overvoltage and of 105 % for the
undervoltage functionality.
Minimum absolute dropout differential
Times
Operate time with time delay = 0 ms
Standard filter, true RMS
2 cycle filters
Dropout time
Standard filter, true RMS
2 cycle filters
Frequency Operating Range
0.9 ≤ f/f
≤ 1.1
rated
10 Hz ≤ f < 0.9 f
1.1 f
< f ≤ 90 Hz
rated
f < 10 Hz
f > 90 Hz
Tolerances
Voltages
Time delays
60
OOT (Output Operating Time) additional delay of the output medium used, see chapter
SIPROTEC 5, Merging Unit 6MU85, Manual
C53000-G5040-C074-1, Edition 01.2020
rated
0.00 s to 60.00 s
0.00 s to 320.00 s
0.90 to 0.99
0.300 V to 200.000 V
0.300 V to 200.000 V
150 mV sec.
60
Approx. 25 ms + OOT
at 50 Hz
Approx. 22 ms + OOT at 60 Hz
Approx. 45 ms + OOT at 50 Hz
Approx. 39 ms + OOT at 60 Hz
Approx. 20 ms + OOT at 50 Hz
Approx. 17 ms + OOT at 60 Hz
Approx. 31 ms + OOT at 50 Hz
Approx. 27 ms + OOT at 60 Hz
According to specified tolerances
Slightly expanded tolerances
Active
0.5 % of the setting value or 0.05 V
1 % of the setting value or 10 ms
12.1.4 Relay Outputs
Technical Data
12.10 Voltage Protection
Increments of 0.01 s
Increments of 0.01 s
Increments of 0.01
Increments of 0.001 V
Increments of 0.001 V
837