Siemens SIPROTEC 5 6MU85 Manual page 10

Advertisement

12.1
General Device Data
Analog Inputs
12.1.1
GIS Low-Power Current Input (via Module IO240)
All current, voltage, and power data are specified as RMS values.
Rated frequency f
Rated current I
rated
Rated current I
rated
Measuring range
Power consumption per current
circuit at rated current
Thermal rating
Accuracy
Voltage Input
All current, voltage, and power data are specified as RMS values.
Rated frequency f
Input and output modules
Measuring range
Burden
Thermal rating
GIS Low-Power Voltage Input (via Module IO240)
All current, voltage, and power data are specified as RMS values.
Rated frequency f
Rated voltage V
Rated voltage V
Measuring range
Power consumption per current
circuit at rated current
Thermal rating
Accuracy
Measuring-Transducer Inputs (via Module ANAI-CA-4EL)
Insulation class
Connector type
SIPROTEC 5, Merging Unit 6MU85, Manual
C53000-G5040-C074-1, Edition 01.2020
50 Hz
rated
60 Hz
- 50 Hz
Min. 13 mV
Max. 332 mV
- 60 Hz
Min. 15.4 mV
Max. 386 mV
50 ⋅ I
rated
1.6 ⋅ I
Max. 40 mVA
Burden = 9.5 kΩ
Max. input voltage = 20 V
Class 5TPE (Protection channel)
Class 0.2S (Metering channel)
50 Hz, 60 Hz
rated
16.7 Hz (for rail devices only)
IO102, IO202, IO208, IO211,
IO214
0 V to 200 V
< 0.1 VA
230 V continuously
50 Hz
rated
60 Hz
- 50 Hz
Min. 0.25 mA
rated
Max. 2.00 mA
- 60 Hz
Min. 0.30 mA
rated
Max. 2.20 mA
2 ⋅ V
rated
Max. 1 mVA
Burden = 50 Ω
Max. input current = 4.4 mA
Class 0.1
SELV (Safety Extra Low Voltage) (according to IEC 60255-27)
8-pin terminal spring
(Protection channel)
(Metering channel)
rated
Technical Data
12.1 General Device Data
IO215
0 V to 7.07 V
< 0.01 VA
20 V continuously
787