Technical Data
12.13 External Trip Initiation
12.13
External Trip Initiation
Setting Values
Tripping delay
Times
Operate time with time delay = 0 ms
- At initiation via binary input signal
Tolerance
Sequence tolerance for delay times
70
OOT (Output Operating Time) additional delay of the output medium used, for example 5 ms with fast relays, see chapter
12.1.4 Relay Outputs
848
0.00 s to 60.00 s
70
Approx. 10 ms + OOT
.
1 % of the setting value or 10 ms
SIPROTEC 5, Merging Unit 6MU85, Manual
C53000-G5040-C074-1, Edition 01.2020
Increments of 0.01 s