Download Print this page

Siemens SIPROTEC 5 6MU85 Manual page 91

Advertisement

Technical Data
12.30 Operational Measured Values and Statistical Values
Power Values
Active power P
Voltage range
Current range
Frequency range
Power factor
Tolerance
Reactive power Q
Voltage range
Current range
Frequency range
Power factor
Tolerance
Apparent power S
Voltage range
Current range
Frequency range
Tolerance
Power Factor
Voltage range
Current range
Frequency range
Tolerance
Frequency
Frequency f
Range
Tolerance
Range
Tolerance
Range
Tolerance
868
W secondary
(0.8 to 1.2) · V
rated
(0.1 to 2) · I
rated
45 Hz to 55 Hz at f
= 50 Hz
rated
55 Hz to 65 Hz at f
= 60 Hz
rated
|cosφ| ≥ 0.707
0.5 % of S
in the above-mentioned measuring
rated
range
var secondary
(0.8 to 1.2) · V
rated
(0.1 to 2) · I
rated
45 Hz to 55 Hz at f
= 50 Hz
rated
55 Hz to 65 Hz at f
= 60 Hz
rated
|cosφ| ≤ 0.707
0.5 % of S
in the above-mentioned measuring
rated
range
VA secondary
(0.8 to 1.2) · V
rated
(0.01 to 2) · I
rated
45 Hz to 55 Hz at f
= 50 Hz
rated
55 Hz to 65 Hz at f
= 60 Hz
rated
0.5 % of S
in the above-mentioned measuring
rated
range
(0.8 to 1.2) · V
rated
(0.1 to 2) · I
rated
45 Hz to 55 Hz at f
= 50 Hz
rated
55 Hz to 65 Hz at f
= 60 Hz
rated
0.02 in the above-mentioned measuring range
Hz
f
- 0.20 Hz ≤ f ≤ f
+ 0.20 Hz
rated
rated
± 2 mHz at V = V
or at I = I
rated
f
- 3.00 Hz ≤ f < f
+ 3.00 Hz
rated
rated
± 5 mHz at V = V
or at I = I
rated
25 Hz to 80 Hz; operational measured values
10 Hz to 90 Hz; functional measured values, system
frequency
± 10 mHz at V = V
or at I = I
rated
SIPROTEC 5, Merging Unit 6MU85, Manual
C53000-G5040-C074-1, Edition 01.2020
rated
rated
rated

Advertisement