12.19
Voltage-Balance Supervision
Setting Values
Release threshold
Threshold min/max
Delay failure indication
Dropout Ratio
Overvoltage dropout ratio
Undervoltage dropout ratio
Times
Tripping time
Dropout time
SIPROTEC 5, Merging Unit 6MU85, Manual
C53000-G5040-C074-1, Edition 01.2020
0.300 V to 170.000 V
0.58 to 0.95
0.00 s to 100.00 s
Technical Data
12.19 Voltage-Balance Supervision
Increments of 0.001 V
Increments of 0.01
Increments of 0.01 s
Approx. 0.97
Approx. 1.05
Approx. 500 ms
Approx. 500 ms
855