Siemens SIPROTEC 5 6MU85 Manual page 26

Advertisement

Times
Pickup time, in the case of an internal start
Pickup time, in the case of an external start
Typical dropout time
Dropout time, via circuit-breaker auxiliary-contact
33
criterion
Frequency Operating Range
0.9 ≤ f/f
≤ 1.1
rated
10 Hz ≤ f < 0.9 f
1.1 f
< f ≤ 90 Hz
rated
f < 10 Hz
f > 90 Hz
Tolerances
Threshold values, dropout thresholds
Times
33
When using transformer connection type 2ph, 2p. CT + IN-sep, slightly expanded tolerances occur
SIPROTEC 5, Merging Unit 6MU85, Manual
C53000-G5040-C074-1, Edition 01.2020
rated
12.3 Circuit-Breaker Failure Protection
< 1 ms
< 5 ms
< 15 ms
< 5 ms
According to specified tolerances
Slightly expanded tolerances
Active
2 % of the setting value or 1 % of the rated current
1 % of the setting value or 10 ms
Technical Data