Technical Data
12.1 General Device Data
Settings
Temperature measuring range
Temperature Inputs (via Module IO240)
Settings
Sensor Type
Measurement range
Accuracy
LPIT Digital Input (via Module IO240)
Shield Cover Input
Sensor type
Measurement type
12.1.2
Supply Voltage
Integrated Power Supply
For modular devices, the following modules contain a power supply:
PS201 – Power supply of the base module and of the 1st device row
PS203 – Power supply of the 2nd device row
PS204 – Redundant power supply
CB202 – Plug-in module assembly with integrated power supply, for example, to accommodate communica-
tion modules
Permissible voltage
ranges
(PS201, PS203, PS204,
CB202)
Auxiliary rated voltage V
(PS201, PS203, PS204,
CB202)
Permissible voltage
ranges (PS101)
Only for non-modular
devices
Auxiliary rated voltage V
(PS101)
Only for non-modular
devices
Superimposed alternating
voltage, peak-to-peak,
IEC 60255-11,
IEC 61000-4-17
Inrush current
790
Value
-65 °C to +710 °C
-50 °C to +250 °C
-50 °C to +250 °C
Value
PT100 (Class F 0.3 EN 60751)
4-wire shielded cable connection
-50 °C to +150 °C
Shot circuit and broken-wire detection
±1 °C
Dry contact input
Output voltage of 1 mA current injection @ max. DC 5 V
DC 19 V to DC 60 V
DC 24 V/DC 48 V
H
DC 19 V to DC 60 V
DC 24 V/DC 48 V
H
≤ 15 % of the DC auxiliary rated voltage (applies only to direct voltage)
≤ 18 A
Note
For PT100
For NI100
For NI120
DC 48 V to DC 300 V
AC 80 V to AC 265 V, 50 Hz/60 Hz
DC 60 V/DC 110 V/DC 125 V/DC 220 V/
DC 250 V or
AC 100 V/AC 115 V/AC 230 V, 50 Hz/60 Hz
DC 48 V to 150 V
DC 60 V/DC 110 V/
DC 125 V
SIPROTEC 5, Merging Unit 6MU85, Manual
C53000-G5040-C074-1, Edition 01.2020
DC 88 V to DC 300 V
AC 80 V to AC 265 V,
50 Hz/60 Hz
DC 110 V/ DC 125 V/
DC 220 V/DC 250 V
or
AC 100 V/AC 115 V/
AC 230 V, 50 Hz/60 Hz

Advertisement