Turn on switching power for 30 s, recovery time until switching on again is 15 minutes.
For short-term switching operations, an impulse/pause ratio of 3 % must be considered.
100 V/9.0 A
60 V/10.0 A
48 V/10.0 A
24 V/10.0 A
AC and DC contact voltage
Permissible continuous current per contact
Permissible current per contact (switching on and
holding)
Short-time current across closed contact
Total permissible current for contacts connected to
common potential
Switching time OOT (Output Operating Time)
Additional delay of the output medium used
Rated data of the output contacts in accordance with
UL certification
Interference suppression capacitors across the
contacts
The power relays operate in interlocked mode, that is, only one relay of each switching pair picks up at a time
thereby avoiding a power-supply short circuit.
ETH-BD-2FO
12.1.5
Description
Product code
Figure
Connector type
Wavelength
Baud rate
SIPROTEC 5, Merging Unit 6MU85, Manual
C53000-G5040-C074-1, Edition 01.2020
1000 W
Continuous and inching operation is not permitted.
600 W
In order to prevent any damage, the external protec-
tion circuit must switch off the motor in case the rotor
480 W
is blocked.
240 W
250 V
5 A
30 A for 1 s
250 A for 30 ms
5 A
≤ 16 ms
DC 300 V, 4.5 A - 30 s ON, 15 min OFF
DC 250 V, 1 hp motor - 30 s ON, 15 min OFF
DC 110 V, 3/4 hp motor - 30 s ON, 15 min OFF
DC 60 V, 10 A, 1/2 hp motor - 30 s ON, 15 min OFF
DC 48 V, 10 A, 1/3 hp motor - 30 s ON, 15 min OFF
DC 24 V, 10 A, 1/6 hp motor - 30 s ON, 15 min OFF
4.7 nF, ± 20 %, AC 250 V
Communication module for the transmission of Ethernet protocols via
2 optical interfaces, suitable for Process-bus client, Merging Unit, and
ultrafast GOOSE
P1Zxxxxxxxxxx
2 x duplex LC
λ = 1300 nm
100 Mbit/s
Technical Data
12.1 General Device Data
795