12.16
Voltage-Jump Detection
Times
Pickup time
Frequency Operating Range
0.9 ≤ f/f
≤ 1.1
rated
10 Hz ≤ f < 0.9 f
1.1 f
< f ≤ 90 Hz
rated
f < 10 Hz
f > 90 Hz
Tolerances
Voltages
Pulse time
72
OOT (Output Operating Time) additional delay of the output medium used, for example 5 ms with fast relays
SIPROTEC 5, Merging Unit 6MU85, Manual
C53000-G5040-C074-1, Edition 01.2020
rated
72
Approx. 10 ms + OOT
at 50 Hz
Approx. 8 ms + OOT at 60 Hz
According to specified tolerances
Slightly expanded tolerances
Inactive
2 % of the setting value or 0.100 V
for amplitude changes of sinusoidal measurands
1 % of the setting value or 10 ms
Technical Data
12.16 Voltage-Jump Detection
851