12.12
2nd Harmonic Detection Ground
Setting Values
Measured value
2nd harmonic content
Times
Operating times
Pickup
Harmonic: I
2nd harm
Dropout
The greater dropout differential (= | pickup threshold – dropout threshold |) of the following
2 criteria applies:
Dropout differential derived from the parameter Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for the overcurrent protection and a dropout
ratio of 105 % applies for the undercurrent protection.
Minimum absolute dropout differential
Protection-class current transformers
Instrument transformers
Harmonics: I
2nd harm
Frequency Operating Range
0.9 ≤ f/f
≤ 1.1
rated
10 Hz ≤ f < 0.9 f
1.1 f
< f ≤ 90 Hz
rated
f < 10 Hz
f > 90 Hz
Tolerances
Harmonics: I
2nd harm
SIPROTEC 5, Merging Unit 6MU85, Manual
C53000-G5040-C074-1, Edition 01.2020
/I
1st harm
/I
1st harm
rated
/I
1st harm
12.12 2nd Harmonic Detection Ground
IN measured
3I0 calculated
10 % to 45 %
Approx. 29 ms
Setting value or at least
I
= 10 mA sec. and
1st harm
I
= 10 mA sec. (I
= 1 A)
2nd harm
rated
I
= 50 mA sec. and
1st harm
I
= 50 mA sec. (I
= 5 A)
2nd harm
rated
15 mA sec. (I
= 1 A) or
rated
75 mA sec. (I
= 5 A)
rated
0.5 mA sec. (I
= 1 A) or
rated
2.5 mA sec. (I
= 5 A)
rated
0.75 or
I
= 5 mA sec. (I
= 1 A) or
2nd harm
rated
I
= 25 mA sec. (I
= 5 A)
2nd harm
rated
According to specified tolerances
Slightly expanded tolerances
Inactive
1 % of the setting value
for setting values l
/
2nd harm
1st harm
Technical Data
Increments of 1%
847