Technical Data
12.30 Operational Measured Values and Statistical Values
12.30
Operational Measured Values and Statistical Values
The following applies to the tolerances of currents and voltages:
The values apply both to the RMS values and the absolute value and phase angle of the fundamental
components.
The values were determined for pure sinusoidal signals – without harmonics.
All measured values have an additional tolerance of 1 DIGIT.
Voltages
V
, V
, V
A
B
C
Voltage range
Secondary rated voltage
Measuring range
Frequency range
Tolerance
Frequency range (expanded)
Tolerance
V
, V
, V
AB
BC
CA
Voltage range
Secondary rated voltage
Measuring range
Frequency range
Tolerance
Frequency range (expanded)
Tolerance
Currents, Instrument Transformers
I
, I
, I
, 3I
A
B
C
0
Current range
Rated currents
Measuring range
Frequency range
Tolerance
866
V secondary
< 200 V secondary
100 V to 125 V
(0.1 to 2) · V
rated
49 Hz to 51 Hz at f
= 50 Hz
rated
59 Hz to 61 Hz at f
= 60 Hz
rated
0.2 % of the measured value in the above-mentioned
measuring range
45 Hz to 55 Hz at f
= 50 Hz
rated
55 Hz to 65 Hz at f
= 60 Hz
rated
0.3 % of the measured value in the above-mentioned
measuring range
V secondary
< 200 V
100 V to 125 V
(0.1 to 2) · V
rated
49 Hz to 51 Hz at f
= 50 Hz
rated
59 Hz to 61 Hz at f
= 60 Hz
rated
0.2 % of the measured value in the above-mentioned
measuring range
45 Hz to 55 Hz at f
= 50 Hz
rated
55 Hz to 65 Hz at f
= 60 Hz
rated
0.3 % of the measured value in the above-mentioned
measuring range
A secondary
< 1.6 I
rated
1 A, 5 A
(0.1 to 1.6) · I
rated
49 Hz to 51 Hz at f
= 50 Hz
rated
59 Hz to 61 Hz at f
= 60 Hz
rated
0.1 % of the measured value in the above-mentioned
measuring range
SIPROTEC 5, Merging Unit 6MU85, Manual
C53000-G5040-C074-1, Edition 01.2020