12.25
Temperature Supervision
Setting Values
Pickup value
Time delay
Dropout
Dropout differential
Tolerances
Tripping delay
Measured temperature value
SIPROTEC 5, Merging Unit 6MU85, Manual
C53000-G5040-C074-1, Edition 01.2020
-50 °C to 250 °C
-58 °F to 482 °F
0 s to 60 s
or ∞
3 °C or 6 °F
±1 % of the setting value or ±10 ms
±0.5 % of the setting value or ±1 °C or ±2 °F
Technical Data
12.25 Temperature Supervision
Increments of 1°C
Increments of 1°F
Increments of 1 s