Technical Data
12.22 Current-Balance Supervision
12.22
Current-Balance Supervision
Setting Values
Release threshold
Threshold min/max
Delay failure indication
Dropout Ratio
Overcurrent dropout ratio
Undercurrent dropout ratio
Times
Tripping time
Dropout time
858
I
= 1 A
rated
I
= 5 A
rated
0.030 A to 35.000 A
0.15 A to 175.00 A
0.10 to 0.95
0.00 s to 100.00 s
Approx. 0.97
Approx. 1.05
Approx. 500 ms
Approx. 500 ms
SIPROTEC 5, Merging Unit 6MU85, Manual
C53000-G5040-C074-1, Edition 01.2020
Increments of 0.001 A
Increments of 0.01 A
Increments of 0.01
Increments of 0.01 s