Download Print this page

Siemens SIPROTEC 5 6MU85 Manual page 14

Advertisement

Integrated Power Supply
Recommended external
protection
Internal fuse
PS101
Only for non-modular
devices
PS201, PS203, CB202
(to device version xA)
PS201, PS203, PS204,
CB202
(Device version xB and
higher)
Power consumption (life relay active)
1/3 module, non-modular
Without plug-in modules
1/3 base module, modular
Without plug-in modules
1/6 expansion module
1/6 plug-in module
assembly without plug-in
modules (modules CB202)
Plug-in module for base
module or plug-in module
assembly (for example,
communication module)
Stored-energy time for auxiliary voltage outage or
short circuit, modular devices
IEC 61000-4-11
IEC 61000-4-29
Stored-energy time for auxiliary voltage outage or
short circuit, non-modular devices
IEC 61000-4-11
IEC 61000-4-29
SIPROTEC 5, Merging Unit 6MU85, Manual
C53000-G5040-C074-1, Edition 01.2020
Miniature circuit breaker 6 A, characteristic C according to IEC 60898
DC 24 V to DC 48 V
4 A inert, AC 250 V,
DC 150 V,
UL recognized
SIBA type 179200 or
Schurter type SPT 5x20
4 A inert, AC 250 V,
DC 150 V,
UL recognized
SIBA type 179200 or
Schurter type SPT 5x20
4 A inert, AC 250 V,
DC 150 V,
UL recognized
SIBA type 179200 or
Schurter type SPT 5x20
DC
7 W
13 W
3 W
3.5 W
< 5 W
DC 60 V to DC 125 V
2 A time-lag, AC 250 V, DC 300 V, UL recognized
SIBA type 179200 or Schurter type SPT 5x20
2 A time-lag, AC 250 V, DC 300 V, UL recognized
SIBA type 179200 or Schurter type SPT 5x20
3.15 A time-lag, AC 250 V, DC 300 V, UL recognized
SIBA type 179200 or Schurter type SPT 5x20
AC 230 V/50 Hz
16 VA
55 VA
6 VA
14 VA
< 6 VA
For V ≥ DC 24 V ≥ 50 ms
For V ≥ DC 110 V ≥ 50 ms
For V ≥ AC 115 V ≥ 50 ms
For V ≥ DC 24 V ≥ 20 ms
For V ≥ DC 60 V ≥ 50 ms
For V ≥ AC 115 V ≥ 200 ms
Technical Data
12.1 General Device Data
DC 24 V to DC 48 V
AC 100 V to AC 230 V
AC 115 V/50 Hz
12.5 VA
40 VA
6 VA
7 VA
< 6 VA
791

Advertisement

loading