REVO C
2PH from 1100A to 2100A
Parameter Name
Alm Out Fn
Choose for which conditions the digital output
indicates alarm. The output always indicate an
alarm when the heat sink is over temperature. The
digital output is energized for normal operating
condition and de-energized when the power
controller is off or when there is an alarm.
Note!: The power controller monitors for heater
break or short circuit condition only when included
in the option selected for Alarm Output Function
Option
Heater Break
Short Circuit
Therm
Communication
FAN
DEFAULT
Alarm Bitwise is allowed
Parameter Name
Retransmit
Choose which parameter is retransmitted by the
analog output
DEFAULT: Power
Description
Heater Break
Short circuit
SCR is over temperature
Communication watchdog error
Indicate that a fan is not working properly or not supplied
Description
Option
Set Point
Set point
Volts Out
RMS voltage output
Power
Average output power
Current
RMS current output
None
Do not retransmit value
Description
Description
48
User's manual
Modbus
Default
Address
1
34
Modbus
Default
Address
12
68
Value
15
10
12
11
0
12
Par.
Type
Read
Write
Bit
0
1
3
4
7
None
Par.
Type
Read
Write