User’s manual REVO S-IFH 1PH from 30A to 40A Important warnings for safety This chapter contains important information for the safety. The not observance of these instructions may result in serious personal injury or death and can cause serious damages to the Thyristor unit and to the components system included.
Page 5
User’s manual REVO S-IFH 1PH from 30A to 40A WARNING! All service including inspection, installation, wiring, maintenance, troubleshooting, fuse or other user serviceable component replacement must be performed only by properly qualified personnel. Service personnel must read this manual before proceeding with work. While service is being performed unqualified personnel should not work on the unit or be allowed in the immediate vicinity.
Page 6
User’s manual REVO S-IFH 1PH from 30A to 40A AVERTISSEMENT! Au moment de relever des mesures de tension ou de courant en direct, utiliser un équipement de protection individuelle approprié pour les tensions et les potentiels d’arc électrique concernés. WARNING! Verify the voltage and current ratings of the power controller are correct for the application. AVERTISSEMENT! Vérifier que les valeurs de tension et de courant du régulateur de puissance sont correctes pour l’application.
Substituted parts remain of Producer property. CD Automation srl assumes no liability for any damage to persons or property deriving from tampering, from incorrect or improper use, or from any use not conforming to the characteristics of the controller and to the instructions in this User Manual.
User’s manual REVO S-IFH 1PH from 30A to 40A Basic Connections Single phase wiring with resistive load I= P V V = Nominal voltage of the load I = Nominal current of the load P = Nominal power of the load Open Delta wiring with resistive load I= P V = Nominal voltage of the load...
User’s manual REVO S-IFH 1PH from 30A to 40A Identification and Order Code 2.1 Identification of the unit Caution: Before to install, make sure that the Thyristor unit have not damages. If the product has a fault, please contact the dealer from which you purchased the product. The identification label give all the information regarding the factory settings of the Thyristor unit, this label is on the unit, like represented in figure.
User’s manual REVO S-IFH 1PH from 30A to 40A Technical Specifications 3.1 General features Cover and Socket material: PolymericV2 Mounting: DIN bar (thickness type 1mm Max) Utilization Category: AC-51 AC-55b IP Code: Method of Connecting: Single Phase load Auxiliary voltage (only with HB option): 24V dc/ac (max 70mA) Delay switch ON/OFF time: 1/2 Period Max...
User’s manual REVO S-IFH 1PH from 30A to 40A 3.4 Environmental installation conditions Ambient temperature 0-40°C (32-104°F) at nominal current. Over 40°C use the derating curve (max 50°C). Storage temperature -25°C to 70°C, -13°F to 158°F Installation place Don’t install at direct sun light, where there are conductive dust, corrosive gas, vibration or water and also in salty environmental.
User’s manual REVO S-IFH 1PH from 30A to 40A Installation Before to install, make sure that the Thyristor unit have not damages. ≥5 cm If the product has a fault, please contact the dealer from which you purchased the product. Verify that the product is the same thing as ordered.
User’s manual REVO S-IFH 1PH from 30A to 40A Wiring instructions The Thyristor unit could be susceptible to interferences lost by near equipments or by the power supply, for this reason in accord to the fundamental practices rules is opportune take some precautions: •...
User’s manual REVO S-IFH 1PH from 30A to 40A 5.2 Access to L1 – T1 terminal Screw 1. Open fuse holder by pulling the frontal cover 2. Fix the wire on Ln 3. Fix the wire on Tn 4. Close the cover by pressing TOP VIEW DOWN VIEW...
User’s manual REVO S-IFH 1PH from 30A to 40A 5.3 Connection Diagram with Flat wiring system (Option) (Max 16 module connection) TU Module POWER not included ALARM CAL Ext. AUX 24V ac/dc CAL Ext. 12-24Vdc HB Alarm 5.4 Led status and Alarms STATUS DESCRIPTION LED OFF (...
User’s manual REVO S-IFH 1PH from 30A to 40A Input setting The input type is already configured in line with customer requirements that are defined in the Order Code. However, if you wish to change the input type (ex. from 0÷10V to 4÷20mA) set the jumpers as below represented and then do the “Input calibration procedure”.
User’s manual REVO S-IFH 1PH from 30A to 40A 6.1 Input calibration procedure (Analog Input option) Warning: this procedure can be done just by specialized personnel and is needed only if you change the input type. Start TUNE Auxiliary power supply Mantain Key CAL pushed and give the power supply 2sec.
User’s manual REVO S-IFH 1PH from 30A to 40A Heater Break alarm and SCR short circuit (HB Option) Caution: to work properly the load must be powered at least about 160msec. The Heater Break circuit read the load current with an Internal current transformer (C.T.). Minimum current is 10% of the current transformer size.
User’s manual REVO S-IFH 1PH from 30A to 40A Firing type 8.1 Zero Crossing (for SSR Input only) ZC firing mode is used with Logic Output from temperature controllers and the Thyristor operates like a contactor. The Cycle time is performed by temperature controller. ZC minimizes interferences because the Thyristor unit switches ON-OFF at zero voltage.
User’s manual REVO S-IFH 1PH from 30A to 40A 8.3 Burst Firing settings The Burst Firing cycles is already configured in line with customer requirements that are defined in the Order Code. However, if you wish to change the Burst Firing cycles (es. from 4 to 8) set the jumpers as below represented: Warning: Before operate, be sure that power and control cables are isolated from voltage sources.
User’s manual REVO S-IFH 1PH from 30A to 40A Internal Fuse The thyristor unit have internal fuse extrarapid at low I²T for the thyristor protection of against the short-circuits. The Fuses must have I²T 20% less than thyristor’s I²T. The warranty of thyristor is null if no proper fuses are used. Fuse Code Total Current I²T at 500Vac*...
User’s manual REVO S-IFH 1PH from 30A to 40A Trouble shooting Small problems sometimes can be solved locally with the help of the below tab of trouble shooting. If you don’t succeed, contact us or your nearest distributor. Possible reasons Symptom Indication on front unit Actions...