CD Automation srl CD3000S-1PH Analog Input from 35A to 110A User’s manual Important warning for safety Thyristor units are used in power industrial equipment. The voltages used in the Thyristor unit can cause severe electrical shock, and could be lethal.
CD Automation srl CD3000S-1PH Analog Input from 35A to 110A User’s manual Quick Start Attention: this procedure must be carried out by skilled people only. If the Order Code of the Thyristor unit is in line with what you really need, then CD3000S has been already configured in Factory and you just need to do the following steps: 1.
CD Automation srl CD3000S-1PH Analog Input from 35A to 110A User’s manual Installation Before to install the CD3000 unit examine for damages or deficiencies. If any is found, notify the carrier immediately. Check that the product features shown on CD3000 cover corresponds to that ordered.
Page 5
CD Automation srl CD3000S-1PH Analog Input from 35A to 110A User’s manual Diagram of control connection 35÷45A 60÷110A L2/N L2/N L2/N L2/N Fan Power Supply (Only for size 110A H.B. Alarm C1 C2 C3 Ext. CAL 12-24Vdc 1 2 3 4 5 6 7 8 H.B.
CD Automation srl CD3000S-1PH Analog Input from 35A to 110A User’s manual Technical Specifications Input features General features 4 ÷ 30Vdc 5mA Max Cover and Socket PolymericV2 (ON 4Vdc Logic input SSR: material: OFF 1Vdc) Heat-sink: Anodized aluminum Analog Input: 0 ÷...
CD Automation srl CD3000S-1PH Analog Input from 35A to 110A User’s manual Heater break alarm and SCR short circuit (HB option) The Heater Break circuit to work properly must have at least an input of 25% of the nominal current.
User’s manual Firing setting The BF firing performed in Digital mode in CD Automation Thyristor unit give a lot of advantages because switches Thyristor at zero voltage crossing (ZC) without EMC interferences. Analog input is necessary for BF and can be decided how many complete Cycle we want at 50% of power demand.
CD Automation srl CD3000S-1PH Analog Input from 35A to 110A User’s manual Input calibration procedure Warning: this procedure can be done just by specialized personnel and is needed only if you change the input type. Start TUNE Auxiliary power supply Mantain Key CAL pushed 2sec.
CD Automation srl CD3000S-1PH Analog Input from 35A to 110A User’s manual Fuses and Fuse holder Warning: High speed fuses are only used for the thyristor protection and can not be used to protect the installation. CD3000S unit must be protected against short circuit by High speed fuses.
(out of range) procedure. Warranty condition CD Automation gives a 12 months warranty to its products. The warranty is limited to repairing and parts substitution in our factory and does exclude products not properly used and fuses. Warranty does not include products with serial numbers deleted.