I< (Lower Limit) - Siemens SIMOCODE 3UF Programming And Operating Manual

Table of Contents

Advertisement

9.2.3
I< (lower limit)
Trip level (CiR), warning level (CiR)
When monitoring Current Limits I< (lower limit), two different response levels (trip
level/warning level) can be parameterized and monitored. Current Limit monitoring is
activated if the current of the phases (Imax) drops below the response level.
Trip level
Warning level
Response, Delay (CiR) at trip level
Here you can set:
● how SIMOCODE pro should respond when the trip level is undershot
● the delay time.
Response
Disabled
Signaling
Warning
Tripping
Delay
Preset
Response, Delay (CiR) at warning level
Here you can set:
● how SIMOCODE pro should respond when the warning level is undershot
● the delay time.
Response
Disabled
Signaling
Warning
Tripping
Delay
Preset
SIMOCODE PRO V PN FDI
Programming and Operating Manual, 05/2020, A5E44499659002A/RS-AA/001
0 to 1020 % of I
in 4 % increments
s
0 to 1020 % of I
in 4 % increments
s
Trip level
X
X
-
X
0 to 25.5 s
0.5 s
Warning level
X
X
X
-
0 to 25.5 s
0.5 s
Monitoring Functions
9.2 Current Limits
51