Monitoring Functions

9.6 0-20 mA - 4-20 mA

9.6
0-20 mA - 4-20 mA
9.6.1
0-20 mA - 4-20 mA
Monitoring 0/4-20 mA
SIMOCODE pro supports two-phase monitoring of the analog signals of a transducer
standard 0/4-20 mA output signal. The analog signals are fed to the "0/4-20mA" function
block via the Analog Module:
Trip Level (CiR), Warning Level (CiR)
With 0/4-20 mA Monitoring, you can parameterize two different response levels (Trip
Level/Warning Level) for the upper and lower limit:
Trip level:
• 0/4-20> (upper limit)
• 0/4-20< (lower limit)
Warning level:
• 0/4-20> (upper limit)
• 0/4-20< (lower limit)
Activity Trip Level, Warning Level
Here you can specify in which motor operating states the Trip Level/Warning Level is to take
effect:
• Always (on)
• Always, except in the case of TPF (on+)
• When the motor is on, except in the case
of TPF (run)
• When the motor is on, except in the case
of TPF, with start hiding (run+)
60
0 - 23,6 mA
0 - 23,6 mA
Trip Level/Warning Level always takes effect,
regardless of whether the motor is running or
stationary
Trip Level/Warning Level always takes effect,
regardless of whether the motor is running or
stationary with the exception of "TPF", i.e.
motor feeder is in test position
Trip Level/Warning Level only takes effect if
the motor is on and not in the test position
The Trip Level/Warning Level only takes
effect if the motor is running and the start-up
procedure is finished, and there is no test
position feedback (TPF)
Programming and Operating Manual, 05/2020, A5E44499659002A/RS-AA/001