Standard Functions; Test - Reset; Test - Siemens SIMOCODE 3UF Programming And Operating Manual

Table of Contents

Advertisement

Standard Functions

12.1

Test - Reset

12.1.1
Test - Reset
Test - Reset
The function of the "TEST/RESET" button on the Basic Unit is generally dependent upon the
operating status of the device:
● Reset function: if a fault occurs
● Test function: in other operating states.
In addition to the TEST/RESET buttons, SIMOCODE pro allows internal Test/Reset tripping
via the Test function block. The Test function block consists of 1 plug.
Overall, there are 2 Test 1 and Test 2 function blocks for BU1 and BU2, whereby each
function block has a slightly different function:
● Test 1: When testing/tripping the output relays
● Test 2: Without tripping the output relays (normally for testing via the bus).
12.1.2

Test

Test
Carrying out testing
Testing can be carried out as following:
● Via the "TEST/RESET" button on the Basic Unit and on the Operator Panel (can be
deactivated) as well as via PC with the Device Integration Manager.
● Via the plugs of the internal Test 1 or Test 2 function blocks.
● Via the menu of the Operator Panel with Display (e.g. the "commands" menu item).
Testing can be terminated at any time - it does not influence the thermal motor
model/overload function, i.e. after switching off via TEST, the system can be reset
immediately. Tripping only occurs for Test 1 when the operating mode is set to "Remote".
SIMOCODE PRO V PN FDI
Programming and Operating Manual, 05/2020, A5E44499659002A/RS-AA/001
12
85

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simocode pro v pn fdi

Table of Contents