Analog Value Recording

16.1

Analog Value Recording - Settings

Analog Value Recording - Settings
Recording is carried out directly in SIMOCODE pro on the basis of the motor feeder and
independently of PROFINET or the automation system. Every analog value present at the
"allocated analog value" analog socket is recorded and saved. The recording starts on the
basis of the edge (positive/negative) via any binary signal at the Trigger Input of the function
block. Up to 60 values can be saved internally in the device.
The time frame of the recording is indirectly determined by the selected sampling rate:
Sampling time = sampling rate [s] x 60 values.
The Pre-trigger can be used to specify how far in advance the recording should commence
before the trigger signal is issued. The Pre-trigger is set as a percentage of the entire
sampling time.
Settings:
Signal/Value
Trigger-Eingang
Allocated analog value
Trigger edge
Sampling rate
Pre-trigger
SIMOCODE PRO V PN FDI
Programming and Operating Manual, 05/2020, A5E44499659002A/RS-AA/001
Range
Analog value recording starts when any signal is issued
(arbitrary sockets , e.g. device inputs, motor current
flowing).
Any value (1 word/2 byte) in SIMOCODE pro
positive / negative
0.1 to 50 s in 0.1-s-increments
0 to 100 % in 5-%-increments
16