Siemens SIMOCODE 3UF Programming And Operating Manual page 66

Table of Contents

Advertisement

Monitoring Functions
9.8 Temperature
Temperature
Response Warning Level T>
Marking Warning Level T>
Hysteresis
Trip level and warning level activity
The trip level/warning level always takes effect, independent of whether the motor is running
or not (operating status "ON").
Response
Overtemperature: Here you can select how SIMOCODE pro should respond when the
temperature has overshot the warning level/trip level.
Response
Disabled
Signaling
Warning
Tripping
Note
With motors for EEx e applications, the response must remain set to "Tripping"!
Note
The sensor type, the number of measuring circuits in use and the response to a sensor fault
must be set in the Temperature Module Inputs (TM Inputs) function block if temperature
monitoring is being used.
Note
To monitor several sensor measuring circuits individually and independently, a suitable
number of free Limit Monitors can be linked to the Temperature Module Inputs function block
and differing limits set for the individual temperature sensors.
66
Description
Set response when the temperature is overshot (see the
following table "response")
No parameters. Optional marking for designating the
signal, e.g. "Temperature >". Range: up to 10 characters
0 to 255°C in 1°C increments (preset: 5°C)
Trip level T>
-
X
-
X
Programming and Operating Manual, 05/2020, A5E44499659002A/RS-AA/001
Warning level T>
X
X
X
-
SIMOCODE PRO V PN FDI